XCD Gas Detector, ATEX/IECEx/Asian approvals, painted 316SS, includes infrared carbon dioxide sensor cartridge 0 to 2.0% v/v

$2,305.00

Description

Also includes 4 to 20 mA output, 2 x M20 entries, nylon weather protection

Sensepoint XCD ATEX/IECEx/China Approvals (316SS) SPXCDASMB1

With remote toxic and Oxygen sensor mounting of up to 100 feet (30m) away from the transmitter, the Honeywell Sensepoint XCD provides a robust monitoring solution even in challenging environments where detection is difficult, including applications where the point of detection is in an area that is not easily accessible or where the detector would not be visible, like in high or low level concealed areas or outside a room being monitored. Its remote capability is designed to offer excellent flexibility of use and is an ideal solution for hard-to-reach locations or areas where the transmitter needs to be separate from the sensor.
  • All-In-One Gas Monitoring Solution 
    • Flammable (catalytic or infrared), toxic and oxygen versions available
    • Serves new/retrofit, indoor/outdoor applications
    • Stainless steel or aluminum explosion-proof housing options
    • IP66 as standard
    Proven and Reliable Sensor Technology 
    • SurecellTM electrochemical sensors
    • Poison immune infrared sensors
    • Poison resistant catalytic bead sensors
    • Long life sensors
    Global Approvals
    • US and Latin America, European, Canadian and Asian
    • Compliant with UL, INMETRO, ATEX,  IECEx, CSA, KTL, PA, GB and CCCF standards
    Easy to Use
    • User friendly and intuitive tri-color backlit display with digits, bar graph and icons
    • Fully configurable via magnetic switches
    • Optional remote sensor mounting
    • Selectable sink or source 4-20mA output
    • Auto-inhibit during maintenance
    • MODBUS communications for remote diagnostics/configuration
    Cost Effective
    • Common transmitter platform
    • Minimal training required
    • Reduced spares
    • Non-intrusive, one-man operation
    • Plug-in sensor replacement
    • MODBUS multi drop option offers cabling savings
    Simple Installation 
    • Plug-in display module removes to give access to terminal area
    • Integral mounting bracket
    • 2 x M20 or ¾” NPT cable/conduit entries
    • Removable plug/socket type terminal blocks for
    • Sink/source switch to suit preferred wiring topology
    • Integral mounting plate attaches to surface, horizontal or vertical piping
  • Industrial manufacturing facilities
  • • Power plants
  • • Waste water facilities
  • • Utilities
  • • Food and beverage production
  • • Refineries and chemical plants
  • • Onshore oil and gas terminals
  • • Production platforms
  • • Exploration and drilling
Use3 wire, 4-20mA and RS485 MODBUS output fixed point detector with in-built alarm and fault relays for the protection of personnel and plant from flammable, toxic and Oxygen hazards. Incorporating a transmitter with local display and fully configurable via non-intrusive magnetic switch interface. Wide range of sensors available.
Electrical
Input Voltage Range16 to 32VDC (24VDC nominal) for ATEX/IECEx/AP Versions
12 to 32VDC (24VDC nominal) for UL/CSA version
Max Power ConsumptionMaximum power consumption is dependent on the type of gas sensor being used. Electrochemical cells = 3.7W, IR = 3.7W and catalytic = 4.9W. Maximum inrush current = 800mA at 24VDC
Current OutputSink or source
≥0.0<1.0mAFault
2.0mA or 4.0mA (17.4mA)Inhibit (during configuration/user settings)
4.0mA to 20.0mANormal gas measurement
22.0mAMaximum over range
Terminals15 x screw terminals suitable for wire diameter 0.5mm2 to 2.5mm2 (20AWG to 13AWG)
Relays3 x 5A@250VAC. Selectable normally open or normally closed (switch) and energised/de-energised (programmable)
Alarm relays default normally open/de-energized. Fault relay default normally open/energized
CommunicationRS485, MODBUS RTU (Optional)
Construction
MaterialHousingEpoxy painted aluminum alloy LM25 or 316 stainless steel
Sensor316 stainless steel
Weather ProtectionPlastic
Weight (approx)Aluminum Alloy LM252.0kg (4.4lbs)
316 Stainless Steel5.0kg (11lbs)
Mounting-Integral mounting plate with 4 x mounting holes suitable for M8 bolts
-Optional pipe mounting kit for horizontal or vertical pipe Ø1.5 to 3" (2" nominal)
EntriesEuropean ATEX/IECEx versions: 2 x M20 cable entries
North American UL/c-UL versions: 2 x ¾"NPT conduit entries. Suitable blanking plug supplied for use if only 1 entry used. Seal to maintain IP rating
Certification
EuropeanATEX II 2 GD Ex d IIC Gb T6 (Ta -40ºC to +65ºC) T5 (Ta -40ºC to +75ºC) Ex tb IIIC T85°C Db IP66 T100ºC (Ta -40ºC to +75ºC)
InternationalIECEx Ex d IIC Gb T6 (Ta -40ºC to +65ºC) T5 (Ta -40ºC to +75ºC) Ex tb IIIC T85°C Db IP66 T100ºC (Ta -40ºC to +75ºC)
ChinaGB Ex d IIC T4 GB3836.1&2 -2000, PA, CCCF
KoreaKTL Ex d IIC T6 (-40°C to +65°C)
North AmericaUL/c-UL - Class I, Division 1, Groups B, C and D, Class I, Division 2, Groups B, C & D, Class II, Division 1, Groups E, F & G, Class II, Division 2, Groups F & G. -40ºC to +65ºC
EMCEN50270:2006 EN6100-6-4:2007
PerformanceATEX, EN60079-29-1:2007 (flammable), EN45544 (Toxic), EN50104 (Oxygen), EN50271
China: PA Pattern Measurement (for transmitter and toxic gas sensors)
“CCCF” Shenyang for Flammable (fire dept approval)
CSA C22.2-152
Environmental
IP RatingIP66 in accordance with EN60529:1992
Certified Temperature Range-40ºC to +75ºC (-40ºF to +167ºF)

Note: The detector display may become illegible at temperatures below -20°C, but the detector continues its gas monitoring function. The display is not damaged and recovers when the temperature rises back above -20°C.
Operating HumidityContinuous 20-90% RH (non-condensing), Intermittent 10-99% RH (non-condensing)
Operating Pressure90-110kPa (EC Toxic Sensors), 80-12kPa (EC Oxygen, Catalytic Bead and Infrared Sensors)
Storage Conditions-25°C to +65°C (-13°F to 131°F)

Additional information

Weight 11 lbs