TPPR System for 19″ Rack System (for Brown Field Sites)

$0.01

19" Rack controller or Remote Unit

5, 7 or 9 Way Communication/Power Rail (Select the appropriate option for your PSU and I/O module combination)

Consists of a DIN Rail blank panel, 1 Ring Coupling Module and 5, 7, or 9 Backplanes

Power Configuration (Select the Power Supply options and I/O Configuration needed)

Input and Output Module (I/O module) 1

The maximum numbers of I/O Modules depend on Communication/Power Rail and Power Configuration selection. Please include a code for each I/O module, including X=None, to make a total of 9 codes. The rail will be populated in the order given below.

Input and Output Module (I/O module) 2

Input and Output Module (I/O module) 3

Input and Output Module (I/O module) 4

Input and Output Module (I/O module) 5

Input and Output Module (I/O module) 6

Input and Output Module (I/O module) 7

Input and Output Module (I/O module) 8

Input and Output Module (I/O module) 9

Customer Logo

X

Customer Set up

For Custom, select the same amount of "Custom" options as you have I/O Modules, as the price is applied per each I/O module.

Product price: $0.01
Total options:
Order total:

Description

TPPR System for 19” Rack (for Brown Field sites)

Use the Touchpoint Pro Part Number and Pricing Configurator design to build flexible 19’’ Rack Control Systems.
19’’ 5U Rack Controller Enclosure
Part NumberTPPR-V-0602
MaterialMild Steel
Earthing PointsM8 (main grounding); other M6
Dimensions (H x W x D)19 in x 8.74 in x 4.33 in (483 mm x 222 mm x 110 mm)
Weight22 lbs (10 kg)
19’’ 5U Rack Remote Unit Enclosure
Part NumberTPPR-V-0612
MaterialMild Steel
Earthing PointsM8 (main grounding); other M6
Dimensions (H x W x D)19 in. x 8.74 in. x 4.33 in. (483 mm x 222 mm x 110 mm)
Weight19.84 lbs (9 kg)
Ring Coupling Module
Ring Coupling Module
Communication / Power Rail
Description5, 7, 9 or 10-way Communication / Power Rail consists of 1 DIN Rail, 1 Ring Coupling Module (RCM), and a 5, 7, 9 or 10-way Backplane
DIN Rail
Total Width16.93 in. (430 mm)
TypeTS-35/15
Ring Coupling Module (RCM)
DescriptionModule for connection of DIN Rail mounted I/O modules to Ring Network
Electrical Connection2 x Ring Network TX / RX Driver Pairs (Each 2-Wire plus Drain)
Supply Voltage24 Vdc (18-32 Vdc)
Power ConsumptionMaximum 1 W
Power DissipationMaximum 1 W
Ring Network CableMinimum 2 x 2 x 1 mm2 twisted pair, plus Drain and Overall Screen
Operating Temperature-40°C to +65°C
Storage Temperature-40°C to +65°C
Environmental Protection ClassPollution Degree 2 (indoor sheltered)
Connector CodingRing cable connectors (TB1-TB4) are coded with coding keys to avoid mis-wiring.
DIN Rail connector (Module Supply and Communication)Maximum Current: 60 mA (18-32 Vdc)
Backplane
Description5, 7, 9 and 10 I/O slot (excluding first slot reserved for RCM) backplane PCB for providing power and Ring Network connections to the RCM and I/O modules
Electrical Connection2-wire (+V and –V) at Power Supply Input for 5, 7, 9 I/O Slot Backplane
2 x 2-wire (+V and –V) at Power Supply Input for 10 I/O Slot Backplane
10-pin backplane connector for connection to RCM and I/O Modules
Maximum Wire Size6 mm2
Supply Voltage24 Vdc (18-32 Vdc)
Backplane current RatingMaximum 20 A
Power Supply Connector RatingMaximum 32 V, 41 A
Backplane connectorMaximum 32 V, 4.04 A
Environmental Protection ClassPollution Degree 2 (indoor sheltered)
Operating Temperature-40°C to +65°C
Storage Temperature-40°C to +65°C
Touchpoint Pro Communication/Power Rail Terminal Identification
Terminal IdentificationLabelChannel
1+Ring A In
2Drain
3-
4+Ring B Out
5Drain
6-
7+Ring B in
8Drain
9-
10+Ring A Out
11Drain
12-
Touchpoint Pro Power Supply Units
Power Supply Units
Power Supply120 W (5A)240 W (10A)480 W (20A)
Input Voltage Range85 - 264 Vac; 88 – 360 Vdc
Input Frequency Range50 - 60 Hz ±6%
Input AC current1.10 A at 120 Vac2.22 A at 120 Vac4.56 A at 120 Vac
0.62 A at 230 Vac1.22 A at 230 Vac2.48 A at 230 Vac
Output Voltage24 Vdc (Adjustable 24 - 28 Vdc)
DC OK Relay contact ratings (max.)60 Vdc 0.3 A / 30 Vdc 1 A / 30 Vac 0.5 A resistive load
ProtectionShort Circuit, Overload (current limiting), No load, Over Voltage, Over Temperature
Dimensions (W x H x D)1.57 in. x 4.88 in. x 4.61 in. (40 mm x 124 mm x 117 mm)2.36 in. x 4.88 in. x 4.61 in. (60 mm x 124 mm x 117 mm)3.23 in. x 4.88 in. x 5 in. (82 mm x 124 mm x 127 mm)
Operating Temperature-25 °C to +70 °C (-13 °F to 158 °F)
Derating (60 °C to 70 °C)3 W/°C6 W/°C12 W/°C
Storage Conditions-40 to +85 °C (-40 °F to 185 °F), 5% to 95% RH
Operating Humidity5% to 95% RH (non-condensing)
Touchpoint Pro 120 W 24 Vdc Power Supply Unit
LabelPurpose
NAC Supply Neutral
LAC Supply Live
Earth
+DC Output +V
+DC Output +V
-DC Output -V
-DC Output -V
DC OKRelay Contact
DC OKRelay Contact
Touchpoint Pro 240 & 480 W 24 Vdc Power Supply Unit
LabelPurpose
NAC Supply Neutral
LAC Supply Live
Earth
+DC Output +V
+DC Output +V
-DC Output -V
-DC Output -V
DC OKRelay Contact
DC OKRelay Contact
Touchpoint Pro Uninterruptible Power Supply Module (UPS)
Uninterruptible Power Supply Module (UPS)
Description23.3 Vdc - 30 Vdc
Input Current70 mA typical internal current consumption
Current consumption for battery charging in constant current mode at 24V input
1.7 A typical at battery selector position <10Ah
3.4 A typical at battery selector position >10Ah
Output Voltage24 Vdc (nominal) in Normal Operation
Adjustable in Battery Operation
Output Currentmax. 25 A in Normal Operations
min. 20 A in Battery Operation
Allowed Batteries2 x 12 V
3.9 Ah – 130 Ah
VRLA lead acid type
Dimensions (W x H x D)1.81 in. x 4.88 in. x 5 in. (46 mm x 124 mm x 127 mm)
Operating Temperature-40°C to +70°C
Derating 60°C to 70°C0.5 A/ºC
Storage Conditions-40°C to +85°C, 5% to 95% RH
Operating Humidity5% to 95% RH (non-condensing)
Touchpoint Pro Backup Battery
Backup Battery
Description24 V sealed lead acid battery, 12 Ah or 27 Ah options
Electrical Connection2 x 12 Vdc batteries in series
Dimensions (W x H x D)15.6 in. x 11.8 in. x 8.5 in. (395 mm x 300 mm x 215 mm)
Weight12 Ah version: 34.6 lbs (15.7 kg)
27 Ah version: 55.1 lbs (25 kg)
Operating Temperature-20°C to +45°C
Operating Humidity10% to 90% RH non condensing
Storage Conditions-20°C to +40°C, 10% to 90% RH
Storage Lifetime without re-charge18 months at <5°C, 6 months at 25°C, 3 months at 30°C, 2 months at 40°C
Ingress ProtectionIP20, NEMA Code 1
Input Voltage (charging)25 Vdc to 28 Vdc (UPS Supervised)
Output Voltage (when supplying)20 Vdc to 28 Vdc (dependent on charge level)
Maximum Input Current3 A
Maximum Output Current20 A
Environmental Protection ClassPollution Degree 2 (indoor sheltered)
Battery TypeFIAMM 12 V 12 Ah FG21202 or FIAMM 12 V 27 Ah FG22703
Fuse Type (inline)Bussman 20 A Fast Acting 1.25” Type ABC-20-R
Current Limit ProtectionDouble pole circuit breaker / Isolator, 20 A
Maximum Altitude2000 m
Touchpoint Pro UPS Connections
The UPS connections are as follows:
Terminal IdentificationLabelPurpose
Input DC 24 V+DC Supply +V
-DC Supply -V
-DC Supply -V (spare)
Output DC 24 V 20 A++V Supply to Touchpoint Pro system
--V Supply to Touchpoint Pro system
Battery+Battery +
-Battery -
Touchpoint Pro UPS Status Relays
The UPS is equipped with status relays as follows:
Terminal IdentificationLabelPurpose
1ReadyContact is closed when both batteries are charged, all OK
2
3BufferingContact is closed when UPS has switched to battery power
4
5Replace BatteryContact is closed when a battery quality fault is detected
6
7InhibitDO NOT USE
8
Touchpoint Pro Analog Input Module mA
Analog Input Module mA
Description4-channel 4-20 mA Analog Input Module with 2 or 3 wire interface to detector
Sensor Configuration4 x 2-wire or 3-wire (current sourced from detector)
Signal Measurement Range0-25 mA
Supply Voltage (Vs)24 Vdc (18-32 Vdc)
Field Device Supply VoltageSupply Voltage (Vs) – 0.7 V
Single Channel Field Device Supply CurrentMaximum 1 A
Total Field Device Supply CurrentTotal Maximum current:2 A at 65°C ambient
Total Maximum current:4 A at 55°C ambient
Power Consumption0.8 W (Excluding sensor supply)
Power DissipationMaximum 3.7 W, at 4 A total field device load
Maximum 2.1 W, at 2 A total field device load
Sense Resistance101 Ω
Connector CodingAnalog Input Module connectors (TB1-TB4) are coded with coding keys to avoid mis-wiring
DIN Rail connector (Module Supply and Communication)Maximum Current:4.04 A (18-32 Vdc)
Touchpoint Pro Analog Input Module mA Terminal Identification
Terminal IdentificationLabelChannelField Device
1+VInput 1+24 Vdc
2SIG4-20 mA signal
3-V0 Vdc
4+VInput 2+24 Vdc
5SIG4-20 mA signal
6-V0 Vdc
7+VInput 3+24 Vdc
8SIG4-20 mA signal
9-V0 Vdc
10+VInput 4+24 Vdc
11SIG4-20 mA signal
12-V0 Vdc
Touchpoint Pro Analog Input Module mV
Analog Input Module mV
Description4-channel Analog Input Module for Catalytic Bridge sensors
Electrical Connection4 x 3-wire mV-Bridge
Supply Voltage24 Vdc (18-32 Vdc)
Sensor Drive methodConstant current
Programmable Current Range180-360 mA
Maximum Loop ResistanceTotal Maximum loop resistance:40 Ω at 200 mA (including Sensor)
Total Maximum loop resistance:27 Ω at 360 mA (including Sensor)
Input Range±15 mV to ±600 mV
Power ConsumptionMaximum 1.2 W (Excluding Sensors)
Power DissipationMaximum 3.5 W
Connector CodingAnalog Input Module connectors (TB1-TB4) are coded with coding keys to avoid mis-wiring
DIN Rail connector (Module Supply and Communication)Maximum Current:1.1 A (18-32 Vdc)
Touchpoint Pro Analog Input Module mV Terminal Identification
Terminal IdentificationLabelChannelField Device
1SInput 1Sensitive (+)
201Signal
3NSNon-sensitive (-)
4SInput 2Sensitive (+)
501Signal
6NSNon-sensitive (-)
7SInput 3Sensitive (+)
801Signal
9NSNon-sensitive (-)
10SInput 4Sensitive (+)
1101Signal
12NSNon-sensitive (-)
Touchpoint Pro Digital Input Module
Digital Input Module
Description4-Channel Digital Input Module for switched input devices
Electrical Connection4 x 2-wire Switch Inputs
Supply Voltage24 Vdc (18-32 Vdc)
Power Consumption1 W maximum (no inputs connected)
Power Dissipation2.8 W maximum
Field Terminals (TB1-TB4) RatingsMaximum current of 14 mA through switched input device at 18-32 Vdc
EOL (End Of Line) Resistance10 kΩ, 0.25 W, ±1%
INL (In-Line) Resistance2.7 kΩ, 0.25 W, ±1%
Switch Input Device supply
Voltage (Vs)
Minimum15 V
Maximum32 V
Switch Input Device supply
Current (Is)
Minimum5 mA for Supervised OC/SC Switch ON condition
Maximum14 mA for Unsupervised Switch ON condition
Connector CodingDigital Input Module connectors (TB1-TB4) are coded with coding keys to avoid mis-wiring
DIN Rail connector (Module Supply and Communication)Maximum Current:95 mA (18-32 Vdc)
Touchpoint Pro Digital Input Module Terminal Identification
Terminal IdentificationLabelChannel
1+Input 1
2
3-
4+Input 2
5
6-
7+Input 3
8
9-
10+Input 4
11
12-
Touchpoint Pro Relay Output Module
Relay Output Module
Description4-channel Relay Output Module incorporating 4 single pole change over (SPCO) relays and 24 Vdc Auxiliary Power Output
Electrical Connection4 x SPCO Relay Terminals (TB1 to TB4)
4 x 2-wire Auxiliary Output Terminals (TB5 to TB8)
Supply Voltage (Vs)24 Vdc (18-32 Vdc)
Auxiliary Supply VoltageSupply Voltage (Vs) – 0.7 V
Auxiliary Supply CurrentMaximum 1.5 A
Power ConsumptionMaximum 1.5 W (excluding auxiliary power consumption)
Power DissipationMaximum 2.3 W
Relay Contacts (TB1-TB4)Maximum 5 A through one relay contact at 250 Vac / 30 Vdc (non-inductive)
Maximum 8 A total through all four relay contacts at 250 Vac / 30 Vdc (non-inductive)
Minimum 12 Vdc, 10 mA
Connector CodingRelay output connectors (TB1-TB4) and auxiliary output connectors (TB5-TB8) are coded with coding keys to avoid mis-wiring.
The relay output connectors (TB1-TB4) are colored black to identify them for AC supply wiring
DIN Rail connector (Module Supply and Communication)Maximum Current:1.62 A (18-32 Vdc)
Touchpoint Pro Relay Output Module Terminal Identification
Terminal IdentificationLabelChannel
1NORelay 1
2NC
3C
4NORelay 2
5NC
6C
7NORelay 3
8NC
9C
10NORelay 4
11NC
12C
13V Aux 1
14+V
15-V
16V Aux 2
17+V
18-V
19V Aux 3
20+V
21-V
22V Aux 4
23+V
24-V

Additional information

Weight 1 lbs