Description
TPPR Power Supply Redundancy Module 40A
A number of power supply options are available, including 120 W, 240 W and 480 W 24 Vdc power supply units, a redundancy module which switches to an alternative supply in the case of failure and a UPS module which charges a back-up battery to be used in the event of a main power failure.
Touchpoint Pro Power Supply Redundancy Module (RDN Module)
Touchpoint Pro Power Supply Redundancy Module (RDN Module) Labels
Power Supply Redundancy Module (RDN Module) | |
---|---|
Description | Suitable for redundant operation of 24 Vdc |
Input Voltage Range | 8.4 - 36.4 Vdc |
Number of Inputs | 2 |
Input Current (max.) | 20 A per input |
Output Reverse Voltage (max.) | 40 Vdc |
Output Current (max.) | 40 A |
Output Voltage Drop | 72mV typical for input: 2x10A |
Dimension | 140mV typical for input: 2x20A |
Operating Temperature (W x H x D) | 1.42 in. x 4.88 in. x 5 in (36 mm x 124 mm x 127 mm) |
Storage Conditions | -40°C to +70°C (-40°F to 158°F) |
Operating Humidity | -40°C to +85°C (-40°F to 185°F), 5% to 95% RH |
5% to 95% RH (non-condensing) |
Label | Purpose |
---|---|
Input 1 + | DC Supply 1 +V |
Input 1 - | DC Supply 1 -V |
Input 2 + | DC Supply 2 +V |
Input 2 - | DC Supply 2 -V |
Output + | DC Output +V |
Output - | DC Output -V |