Description
Consists of a DIN Rail blank panel, 1 Ring Coupling Module and 10 Backplanes
Touchpoint Pro Communication/Power Rail
- Description
- Specifications
- Documentation
- Enclosures
- Power Supply Units
- Spare Parts
- Individual Components
Power distribution for the Touchpoint Pro is via the Communication/Power Rail.
The Touchpoint Pro Communication/Power Rail provides direct power and network connection to the Input/Output modules, minimizing the wiring required. There is a single connection for the 24 Vdc supply and the network cables connect to the Ring Coupling module, which handles the communication between the modules and the central controller.
Depending on the power supply option chosen and the enclosure version, the Communication/Power Rail has space for 5, 7, 9, or 10 Input/Output modules. The Ring Network is the communication link between all Input/Output modules in a Touchpoint Pro system and the central controller. The Ring Network is the only connection required between a local Touchpoint Pro unit (containing the central controller and user interface) and remote Touchpoint Pro units. The Ring Network is implemented for redundancy as two loops transmitting in opposite directions (Ring A and Ring B). The network is self-healing since each module only communicates with the one next to it. If a module fails, the modules after it continue to transmit data in the direction away from the failed module, while the ones before it transmit in the other direction. Thus the Touchpoint Pro system can immediately detect and locate a failed module, without affecting the availability of the rest of the system.
The Touchpoint Pro Input/Output plug-in modules can be combined up to a maximum of 16 input modules (64 channels) and 32 output modules (128 channels). Modules can be located in any Touchpoint Pro enclosure and Touchpoint Pro accepts analog, digital and relay modules, making it one of the most flexible controllers available.
The Touchpoint Pro Communication/Power Rail provides direct power and network connection to the Input/Output modules, minimizing the wiring required. There is a single connection for the 24 Vdc supply and the network cables connect to the Ring Coupling module, which handles the communication between the modules and the central controller.
Depending on the power supply option chosen and the enclosure version, the Communication/Power Rail has space for 5, 7, 9, or 10 Input/Output modules. The Ring Network is the communication link between all Input/Output modules in a Touchpoint Pro system and the central controller. The Ring Network is the only connection required between a local Touchpoint Pro unit (containing the central controller and user interface) and remote Touchpoint Pro units. The Ring Network is implemented for redundancy as two loops transmitting in opposite directions (Ring A and Ring B). The network is self-healing since each module only communicates with the one next to it. If a module fails, the modules after it continue to transmit data in the direction away from the failed module, while the ones before it transmit in the other direction. Thus the Touchpoint Pro system can immediately detect and locate a failed module, without affecting the availability of the rest of the system.
The Touchpoint Pro Input/Output plug-in modules can be combined up to a maximum of 16 input modules (64 channels) and 32 output modules (128 channels). Modules can be located in any Touchpoint Pro enclosure and Touchpoint Pro accepts analog, digital and relay modules, making it one of the most flexible controllers available.
Touchpoint Pro Communication / Power Rail Terminal Identification
Touchpoint Pro Ring Coupling Module
Touchpoint Pro Input/Output Modules Common Specifications
Touchpoint Pro Analog Input Module mA
Touchpoint Pro Analog Input Module mA Terminal Identification
Touchpoint Pro Analog Input Module mV
Touchpoint Pro Analog Input Module mV Terminal Identification
Touchpoint Pro Digital Input Module
Touchpoint Pro Digital Input Module Terminal Identification
Touchpoint Pro Relay Output Module
Touchpoint Pro Relay Output Module Terminal Identification
Terminal Identification | Label | Channel |
---|---|---|
1 | + | Ring A In |
2 | Drain | |
3 | - | |
4 | + | Ring B Out |
5 | Drain | |
6 | - | |
7 | + | Ring B in |
8 | Drain | |
9 | - | |
10 | + | Ring A Out |
11 | Drain | |
12 | - |
Ring Coupling Module | |
---|---|
Communication / Power Rail | |
Description | 5, 7, 9 or 10-way Communication / Power Rail consists of 1 DIN Rail, 1 Ring Coupling Module (RCM), and a 5, 7, 9 or 10-way Backplane |
DIN Rail | |
Total Width | 16.93 in. (430 mm) |
Type | TS-35/15 |
Ring Coupling Module (RCM) | |
Description | Module for connection of DIN Rail mounted I/O modules to Ring Network |
Electrical Connection | 2 x Ring Network TX / RX Driver Pairs (Each 2-Wire plus Drain) |
Supply Voltage | 24 Vdc (18-32 Vdc) |
Power Consumption | Maximum 1 W |
Power Dissipation | Maximum 1 W |
Ring Network Cable | Minimum 2 x 2 x 1 mm2 twisted pair, plus Drain and Overall Screen |
Operating Temperature | -40°C to +65°C |
Storage Temperature | -40°C to +65°C |
Environmental Protection Class | Pollution Degree 2 (indoor sheltered) |
Connector Coding | Ring cable connectors (TB1-TB4) are coded with coding keys to avoid mis-wiring. |
DIN Rail connector (Module Supply and Communication) | Maximum Current: 60 mA (18-32 Vdc) |
Backplane | |
Description | 5, 7, 9 and 10 I/O slot (excluding first slot reserved for RCM) backplane PCB for providing power and Ring Network connections to the RCM and I/O modules |
Electrical Connection | 2-wire (+V and –V) at Power Supply Input for 5, 7, 9 I/O Slot Backplane |
2 x 2-wire (+V and –V) at Power Supply Input for 10 I/O Slot Backplane | |
10-pin backplane connector for connection to RCM and I/O Modules | |
Maximum Wire Size | 6 mm2 |
Supply Voltage | 24 Vdc (18-32 Vdc) |
Backplane current Rating | Maximum 20 A |
Power Supply Connector Rating | Maximum 32 V, 41 A |
Backplane connector | Maximum 32 V, 4.04 A |
Environmental Protection Class | Pollution Degree 2 (indoor sheltered) |
Operating Temperature | -40°C to +65°C |
Storage Temperature | -40°C to +65°C |
Input/Output Modules Common Specifications | |
---|---|
Dimensions (W x H x D) | 1.38 in. x 3.92 in. x 4.51 in. (35.0 mm x 99.5 mm x 114.5 mm) |
Installation | 5, 7, 9 or 10-way Communication / Power Rail |
Maximum Wire Size | 2.5 mm2 |
IP Rating | IP20 |
EMC | EN 50270 |
Power Supply | 18-32 Vdc (24 Vdc nominal) |
DIN Rail Compatibility | TS-35 / 15 |
Casing Material | Polyamide PA 6.6 V0 (UL94) |
Operating Temperature Range | -40°C to 65°C |
Storage Conditions | -40°C to 65°C |
Operating Humidity Range | 10 to 90% RH (non-condensing) |
Weight | 0.46 lbs (210 g) |
Environmental Protection Class | Pollution Degree 2 (indoor sheltered) |
Analog Input Module mA | ||
---|---|---|
Description | 4-channel 4-20 mA Analog Input Module with 2 or 3 wire interface to detector | |
Sensor Configuration | 4 x 2-wire or 3-wire (current sourced from detector) | |
Signal Measurement Range | 0-25 mA | |
Supply Voltage (Vs) | 24 Vdc (18-32 Vdc) | |
Field Device Supply Voltage | Supply Voltage (Vs) – 0.7 V | |
Single Channel Field Device Supply Current | Maximum 1 A | |
Total Field Device Supply Current | Total Maximum current: | 2 A at 65°C ambient |
Total Maximum current: | 4 A at 55°C ambient | |
Power Consumption | 0.8 W (Excluding sensor supply) | |
Power Dissipation | Maximum 3.7 W, at 4 A total field device load | |
Maximum 2.1 W, at 2 A total field device load | ||
Sense Resistance | 101 Ω | |
Connector Coding | Analog Input Module connectors (TB1-TB4) are coded with coding keys to avoid mis-wiring | |
DIN Rail connector (Module Supply and Communication) | Maximum Current: | 4.04 A (18-32 Vdc) |
Terminal Identification | Label | Channel | Field Device |
---|---|---|---|
1 | +V | Input 1 | +24 Vdc |
2 | SIG | 4-20 mA signal | |
3 | -V | 0 Vdc | |
4 | +V | Input 2 | +24 Vdc |
5 | SIG | 4-20 mA signal | |
6 | -V | 0 Vdc | |
7 | +V | Input 3 | +24 Vdc |
8 | SIG | 4-20 mA signal | |
9 | -V | 0 Vdc | |
10 | +V | Input 4 | +24 Vdc |
11 | SIG | 4-20 mA signal | |
12 | -V | 0 Vdc |
Analog Input Module mV | ||
---|---|---|
Description | 4-channel Analog Input Module for Catalytic Bridge sensors | |
Electrical Connection | 4 x 3-wire mV-Bridge | |
Supply Voltage | 24 Vdc (18-32 Vdc) | |
Sensor Drive method | Constant current | |
Programmable Current Range | 180-360 mA | |
Maximum Loop Resistance | Total Maximum loop resistance: | 40 Ω at 200 mA (including Sensor) |
Total Maximum loop resistance: | 27 Ω at 360 mA (including Sensor) | |
Input Range | ±15 mV to ±600 mV | |
Power Consumption | Maximum 1.2 W (Excluding Sensors) | |
Power Dissipation | Maximum 3.5 W | |
Connector Coding | Analog Input Module connectors (TB1-TB4) are coded with coding keys to avoid mis-wiring | |
DIN Rail connector (Module Supply and Communication) | Maximum Current: | 1.1 A (18-32 Vdc) |
Terminal Identification | Label | Channel | Field Device |
---|---|---|---|
1 | S | Input 1 | Sensitive (+) |
2 | 01 | Signal | |
3 | NS | Non-sensitive (-) | |
4 | S | Input 2 | Sensitive (+) |
5 | 01 | Signal | |
6 | NS | Non-sensitive (-) | |
7 | S | Input 3 | Sensitive (+) |
8 | 01 | Signal | |
9 | NS | Non-sensitive (-) | |
10 | S | Input 4 | Sensitive (+) |
11 | 01 | Signal | |
12 | NS | Non-sensitive (-) |
Digital Input Module | ||
---|---|---|
Description | 4-Channel Digital Input Module for switched input devices | |
Electrical Connection | 4 x 2-wire Switch Inputs | |
Supply Voltage | 24 Vdc (18-32 Vdc) | |
Power Consumption | 1 W maximum (no inputs connected) | |
Power Dissipation | 2.8 W maximum | |
Field Terminals (TB1-TB4) Ratings | Maximum current of 14 mA through switched input device at 18-32 Vdc | |
EOL (End Of Line) Resistance | 10 kΩ, 0.25 W, ±1% | |
INL (In-Line) Resistance | 2.7 kΩ, 0.25 W, ±1% | |
Switch Input Device supply Voltage (Vs) | Minimum | 15 V |
Maximum | 32 V | |
Switch Input Device supply Current (Is) | Minimum | 5 mA for Supervised OC/SC Switch ON condition |
Maximum | 14 mA for Unsupervised Switch ON condition | |
Connector Coding | Digital Input Module connectors (TB1-TB4) are coded with coding keys to avoid mis-wiring | |
DIN Rail connector (Module Supply and Communication) | Maximum Current: | 95 mA (18-32 Vdc) |
Terminal Identification | Label | Channel |
---|---|---|
1 | + | Input 1 |
2 | ||
3 | - | |
4 | + | Input 2 |
5 | ||
6 | - | |
7 | + | Input 3 |
8 | ||
9 | - | |
10 | + | Input 4 |
11 | ||
12 | - |
Relay Output Module | ||
---|---|---|
Description | 4-channel Relay Output Module incorporating 4 single pole change over (SPCO) relays and 24 Vdc Auxiliary Power Output | |
Electrical Connection | 4 x SPCO Relay Terminals (TB1 to TB4) | |
4 x 2-wire Auxiliary Output Terminals (TB5 to TB8) | ||
Supply Voltage (Vs) | 24 Vdc (18-32 Vdc) | |
Auxiliary Supply Voltage | Supply Voltage (Vs) – 0.7 V | |
Auxiliary Supply Current | Maximum 1.5 A | |
Power Consumption | Maximum 1.5 W (excluding auxiliary power consumption) | |
Power Dissipation | Maximum 2.3 W | |
Relay Contacts (TB1-TB4) | Maximum 5 A through one relay contact at 250 Vac / 30 Vdc (non-inductive) | |
Maximum 8 A total through all four relay contacts at 250 Vac / 30 Vdc (non-inductive) | ||
Minimum 12 Vdc, 10 mA | ||
Connector Coding | Relay output connectors (TB1-TB4) and auxiliary output connectors (TB5-TB8) are coded with coding keys to avoid mis-wiring. | |
The relay output connectors (TB1-TB4) are colored black to identify them for AC supply wiring | ||
DIN Rail connector (Module Supply and Communication) | Maximum Current: | 1.62 A (18-32 Vdc) |
Terminal Identification | Label | Channel |
---|---|---|
1 | NO | Relay 1 |
2 | NC | |
3 | C | |
4 | NO | Relay 2 |
5 | NC | |
6 | C | |
7 | NO | Relay 3 |
8 | NC | |
9 | C | |
10 | NO | Relay 4 |
11 | NC | |
12 | C | |
13 | V Aux 1 | |
14 | +V | |
15 | -V | |
16 | V Aux 2 | |
17 | +V | |
18 | -V | |
19 | V Aux 3 | |
20 | +V | |
21 | -V | |
22 | V Aux 4 | |
23 | +V | |
24 | -V |