Description
GD-70D SSU Sensor
SSU Gas Detected | Detection Range | Alarm 1 | Alarm 2 | Increments | Part # |
---|---|---|---|---|---|
TMS (Tetramethyl silane) | 0 - 15.0 ppm | 10.0 ppm | 10.0 ppm | 0.1 ppm | GD-70DPLN-TMS |
TRIMS (Trimethyl silane) | 0 - 15.0 ppm | 10.0 ppm | 10.0 ppm | 0.1 ppm | GD-70DPLN-3MS |
TEOS (Tetraethyl orthosilicate) | 0 - 15.0 ppm | 10.0 ppm | 10.0 ppm | 0.1 ppm | GD-70DP-TEOS |
ESU | ESU + PLU *1 | SSU + PLU *1 | NCU | SGU | |
---|---|---|---|---|---|
Detection principle | Electrochemical type | Pyrolysis-particle type | New ceramic (Catalytic combustion) | Semiconductor | |
Gas to be detected | Refer to list of detectable gases | NF3/COS | 0-15ppm TEOS in air and others | Combustible gas | Combustible gas |
Toxic gas | |||||
Detection range | See Detection Gas chart | ||||
Detection method | Pump suction type | Pump suction type/pyrolysis type | Pump suction type | ||
Alarm setpoint value | See Detection Gas chart | ||||
Alarm accuracy | Within ±30% to the alarm setpoint value | ±25% to the alarm setpoint value | Combustible: ±25% to the alarm setpoint value | ||
Toxic: ±30% to the alarm setpoint value | |||||
Alarm delay time | 60 seconds or less by providing the gas 1.6 times the alarm setpoint (excluding delay in the tube and in the communication) | 30 seconds or less by providing the gas 1.6 times the alarm setpoint (excluding delay in the tube and in the communication) | Combustible: 30 seconds or less by providing the gas 1.6 times the alarm setpoint (excluding delay in the tube and in the communication) | ||
Toxic: 60 seconds or less by providing the gas 1.6 times the alarm setpoint (excluding delay in the tube and in the communication) | |||||
Alarm type | Two-step alarm (H-HH) | ||||
Power consumption | Approx. 1.5 W (Max. 4 W) | Approx. 3W (Max. 5.5W) | Approx. 2.5W (Max. 5W) | ||
Power consumption (EA) | 24 V: Approx. 3W (Max. approx. 5W) | 24 V: Approx. 4.5W (Max. approx. 6.5W) | 24 V: Approx. 4W (Max. approx. 6W) | ||
PoE: Approx. 4.5W (Max. approx. 7W) | PoE: Approx. 5.5W (Max. approx. 8.5W) | PoE: Approx. 5.5W (Max. approx. 7W) | |||
Power consumption (DV) | Approx. 2 W (Max. 4.5 W) | Approx. 3.5W (Max. 6W) | Approx. 3W (Max. 5.5W) | ||
Operating temperature (at a constant condition) | 0 - 40ºC | 0 - 40ºC | 0 - 40ºC | 0 - 40ºC | 0 - 40ºC |
Operating humidities (Non-condensing) | 30 - 70%RH | 30 - 80%RH | 95%RH or less | ||
Self diagnosis function | Sensor trouble, system failure | ||||
Date logging function | Event history, alarm history, calibration history, Alarm trend (60 sec. before/after 1st alarm) |