Sensepoint XCL H2 (ppm), 4~20 mA, Charcoal

$975.00

Description

Sensepoint XCL H2 (ppm) SPLCG1BAXCXNZZ

The Honeywell Sensepoint XCL is a fixed gas detector that delivers the safety and compliance you expect — plus the affordability and ease of use that you don’t. It was designed especially for commercial and light industrial applications, delivering just the right amount of functionality to protect people on your premises and ensure compliance with regulations. Sensepoint XCL combines a simple yet robust mechanical housing with a gas detector app, so you can use everyday technology to set up and maintain your gas detector — and quickly get back to business. Sensepoint XCL is available as a flammable gas detector for the detection of potentially explosive gases, or as a toxic gas detector for the detection of a range of toxic gas hazards commonly found in commercial premises.
  • Powerful Connected Interface
    • Smartphone app enables commissioning and maintenance
    • Reporting by device and for site can be emailed direct from the app
  • Cost-effective
    • Efficient install and maintenance to reduce labor/installation costs
    • Affordably priced for commercial spaces
  • Thoughtful, award-winning design
    • Simple, robust housing with our easiest ever installation and maintenance
    • Aesthetic design blends in to the environment
    • Integral gassing port for hard-to-reach locations
    • Compatible with Touchpoint Plus and other industry-standard controllers
  • Parking Garages
  • Hospitals/Laboratories
  • Boiler/Mechanical Rooms
  • Commercial Kitchens
  • Loading Bays
  • Condominiums
  • Offices
  • Food Processing/Bottling
  • Bus Stations
Physical Properties
Dimensions113 x 113 x 59 mm (4.4 x 4.4 x 2.3 in)
Weight500 g (1.1 lb)
Casing MaterialPolycarbonate (charcoal or white)
Ingress Protection RatingIP65, Type 4 (in accordance with NEMA 250)
Lifetime10 years (excludes sensor)
Available Sensors
Flammable, Toxic Gases and Oxygen RangesCombustible0 to 100% LEL (factory calibrated to Methane)
O₂0 to 25% vol
CO300 ppm (adjustable between 50 and 1000 ppm)
H₂1000 ppm
H₂S Low Range50 ppm (adjustable between 10 and 50 ppm)
H₂S High Range100 ppm (adjustable between 50 and 200 ppm)
NO₂20 ppm (adjustable between 5 and 50 ppm)
NH₃200 ppm (adjustable between 50 and 200 ppm)
CO2 (ppm range)5,000 ppm (adjustable between 1,000 and 5,000 ppm)
CO2 (% vol range)5.0% vol (adjustable between 1.0 and 5.0% vol)
Power Supply
Nominal DC Input Voltage24 V DC
Nominal AC Input Voltage24 V AC, 50/60 Hz
Maximum Inrush Current850 mA
Output
Analog Output0 to 22 mA
Digital OutputModbus RTU
Relay Output2 relays rated at 24 V DC / 240 V AC, 5 A
Maximum Power Consumption
mA Versions< 1.2 W (toxic), < 1.7 W (flammable and CO2)
Modbus Versions< 0.7 W (toxic), < 1.2 W (flammable and CO2)
Relay VersionsAdditional 0.6 W total
Connection
TypePluggable rising clamp style, 0.5 to 1.5 mm^2, 20 to 16 AWG.
User Interface
Visual IndicatorMulti-color LED light ringGreen: normal
Flashing red: Alarm
Flashing green and yellow: Warning
Flashing yellow: Fault
Solid yellow: Inhibited
Flashing blue: Bluetooth pairing in
progress
Solid blue: Bluetooth connection
established
Wireless InterfaceBluetooth 4.0 (Bluetooth Low Energy). Dedicated mobile app, enabling wireless configuration and maintenance. Connect up to 10 m away (mobile device dependent). Use a compatible smartphone or other mobile device running Android 4.3 or above.
Operating Environment
Operating Temperature−20 to 50°C (−4 to 122 °F) 0 to 30°C
Storage Temperature(32 to 86 °F)
Humidity15 to 90% RH (non-condensing)
Atmospheric Pressure90 to 110 kPa
Approvals
Electrical SafetyEN/UL/IEC61010-1 CSA-C22.2 No. 61010-1-12
EMCEN 50270
RadioRED, FCC
OtherUL2075 (CO and CH4), AS 1668.2

Additional information

Weight 1.1 lbs
Dimensions 4.4 × 4.4 × 2.3 in