Description
Relay Output Module (4 channels per module)
The Touchpoint Pro Input/Output modules can be combined up to a maximum of 16 input
modules (64 channels) and 32 output modules (128 channels). Modules can be located in
any Touchpoint Pro enclosure. Power distribution is via the Communication/Power Rail.
Touchpoint Pro Relay Output Module
Touchpoint Pro Relay Output Module Terminal Identification
Relay Output Module | ||
---|---|---|
Description | 4-channel Relay Output Module incorporating 4 single pole change over (SPCO) relays and 24 Vdc Auxiliary Power Output | |
Electrical Connection | 4 x SPCO Relay Terminals (TB1 to TB4) | |
4 x 2-wire Auxiliary Output Terminals (TB5 to TB8) | ||
Supply Voltage (Vs) | 24 Vdc (18-32 Vdc) | |
Auxiliary Supply Voltage | Supply Voltage (Vs) – 0.7 V | |
Auxiliary Supply Current | Maximum 1.5 A | |
Power Consumption | Maximum 1.5 W (excluding auxiliary power consumption) | |
Power Dissipation | Maximum 2.3 W | |
Relay Contacts (TB1-TB4) | Maximum 5 A through one relay contact at 250 Vac / 30 Vdc (non-inductive) | |
Maximum 8 A total through all four relay contacts at 250 Vac / 30 Vdc (non-inductive) | ||
Minimum 12 Vdc, 10 mA | ||
Connector Coding | Relay output connectors (TB1-TB4) and auxiliary output connectors (TB5-TB8) are coded with coding keys to avoid mis-wiring. | |
The relay output connectors (TB1-TB4) are colored black to identify them for AC supply wiring | ||
DIN Rail connector (Module Supply and Communication) | Maximum Current: | 1.62 A (18-32 Vdc) |
Terminal Identification | Label | Channel |
---|---|---|
1 | NO | Relay 1 |
2 | NC | |
3 | C | |
4 | NO | Relay 2 |
5 | NC | |
6 | C | |
7 | NO | Relay 3 |
8 | NC | |
9 | C | |
10 | NO | Relay 4 |
11 | NC | |
12 | C | |
13 | V Aux 1 | |
14 | +V | |
15 | -V | |
16 | V Aux 2 | |
17 | +V | |
18 | -V | |
19 | V Aux 3 | |
20 | +V | |
21 | -V | |
22 | V Aux 4 | |
23 | +V | |
24 | -V |