Optima Plus Gas Detector, hydrocarbon version for sampling systems, HART over 4 to 20mA output, FM/CSA

$3,252.00

Description

Also includes 3/4″ thread spigot, electro polished 316SS, and black anodized aluminum flow housing.

Searchpoint Optima Plus Hydrocarbon UL/CSA/Inmetro

The Honeywell Searchpoint Optima Plus is a hazardous area certified flammable infrared gas detector. Infrared gas detectors are ideal for applications in the harshest environments or where catalytic poisons may be routinely present. Searchpoint Optima Plus has the fastest speed of response combined with the highest reliability and reduced routine maintenance. Two versions are available: a hydrocarbon unit and an ethylene unit that can detect a wide range of hydrocarbon gases including solvents.
• Experience gained from over 100,000 units installed worldwide

• Improved reliability

• Optional HART over 4-20mA output

• Can detect a wide range of hydrocarbon gases including solvents

• Increased reliability with no moving parts

• Increased stability from self compensating optics

• Immune to long term component drift

• Remote functional gas test facility

• Certified for North American and European Hazardous areas

• Increased false alarm rejection

• Increased uptime with contaminated optics warning

• Dynamic Heating Control ensures condensation free optics

• No undetected failures

• Improved diagnostics

• Integral event logging

• Reduced power consumption

• Certified to many hazardous area classification schemes including: UL, CSA, ATEX, IECEx and more
  • Offshore oil and gas platforms
  • Floating production storage and offloading (FPSO) vessels
  • Tankers
  • Onshore oil and gas terminals
  • Refineries
  • LNG/LPG bottling plants
  • Gas compressor/metering stations
  • Gas turbine power plants
  • Solvent printing and coating plants
UseSearchpoint Optima Plus is an advanced, Point-Infrared, flammable gas detector certified for use in potentially explosive atmospheres
Measuring Range0-100% LEL, wide selection of Hydrocarbon gas and vapor calibrations. Different measuring ranges and solvent calibrations available for specialist applications
Signal Output4-20mA autosensing sink or source
Inhibit1-3mA (Default 2mA)
Warning0-6mA (Default 3mA*)*Note for ATEX compliance the warning value should not be set between 3 and 5mA
Fault0mA (HART units adjustable to 1mA)
Over Range20-21.5mA (Default 21mA)
Digital OutputOptional Multidrop Modbus RS485 (via DX100(M)), Optional HART over 4-20mA output (HART version 7)
Material316 stainless steel
Weight3.53 lbs (1.6 kg)
AccuracyOptima Plus (Hydrocarbon)Baseline < ±1% FSD, 50% FSD <±2% FSD
Optima Plus (Ethylene)Baseline < ±2% FSD, 50% FSD <±3% FSD
Repeatability< ±2% FSD at 50% FSD
Linearity< 5% FSD
Response TimeT50 < 3 seconds
T90 < 4 seconds (methane)
Operational and Certified-40°C to +65°C temperature range
Long Term Stability (as defined in EN 60079-29-1)BaselineMethane 100% LEL Range: ≤ ± 2% FSD
Ethylene 100% LEL Range: ≤ ± 4% FSD
50% FSDMethane 100% LEL Range: ≤ ± 4% FSD
Ethylene 100% LEL Range: ≤ ± 5% FSD
Drift Over Temperature Range (-40 °C to 65 °C)Baseline≤ ± 2% FSD
50% FSD Methane 100% LEL Range: ≤ ± 0.131% FSD per °C
Ethylene 100% LEL Range: ≤ ± 0.078% FSD per °C
Variation with Pressure0.1% (of reading) per mbar
Power Supply18-32 Vdc (24 Vdc nom), < 4.5W max
Environmental Protection IP 66 / 67
Diagnostics (and Re-calibration)Via certified Hand-held Interrogator, or optional HART communications
Safety ApprovalsUL / CSA: Class 1, Div 1, groups B, C, and D (-40°C to +65°C)
IECEx:Ex d IIC tb IIIC T86°C (Tamb -40°C to +55°C) or T96°C (Tamb -40°C to +65°C) IP66/67
ATEX:BAS99ATEX2259X
II 2 GD Ex d IIC Gb Ex tb IIIC Db
T96°C (Tamb -40°C to +65°C)
T86°C (Tamb -40°C to +55°C)
IP 66/67
Performance ApprovalsCSA C22.2 152., FM ANSI/ISA-12.13.01., EN 60079-29-1 (BVS 03 ATEX G 016 X)
Functional SafetyIEC61508 Safety Integrity Level 2
EMC Compliance SoftwareEN 50270:2006
EN 50271:2010
Marine ApprovalsMarine Equipment Directive (MED), type approvals from DNV, BV, ABS, Lloyd’s Register
Gas Curves (UL/CSA/INMETRO): Calibrated using EN50054 LEL Values
Full ScaleLEL (%V/V)3rd Party ApprovedPart Number
Standard GasesMethane100% LEL5Y2108D3001
Ethane100% LEL32108D3002
Propane100% LEL2Y2108D3004
Butane100% LEL1.5Y2108D3005
Special GasesPropene100% LEL22108D3006
Acetone100% LEL2.152108D3012
Butan-1-ol100% LEL1.42108D3018
Butyl acetate100% LEL1.22108D3020
Butanone100% LEL1.82108D3023
Cyclohexane100% LEL1.22108D3024
Cyclohexanone100% LEL1.32108D3026
Ethanol100% LEL3.32108D3028
Ethyl acetate100% LEL2.12108D3030
Heptane100% LEL1.12108D3032
Hexane100% LEL1.22108D3034
Methanol100% LEL5.52108D3040
Toluene100% LEL1.22108D3042
o-Xylene100% LEL12108D3044
Diethyl ether100% LEL1.72108D3048
p-Xylene100% LEL12108D3054
Pentanes100% LEL1.42108D3056
Dimethyl ether100% LEL32108D3059
N,N-Dimethyl formamide (DMF)100% LEL2.22108D3064
Propane100% LEL2Y2108D3073
Target GasOptima Plus Gas Reference Calibration
152A Difluoroethane (C2H4F2) Band C
Aeron A-31 isobutane (C4H10)Butane (C4H10)
Aeron A-46 LPG (C3H8)Butane (C4H10)
Allyl alcohol (C3H6O)Band C
Amyl alcohol (C5H11OH)Band C
Benzene (C6H6)Ethylene (C2H4) 0-100% LEL
Butadiene dimer (C8H12)Ethylene (C2H4) 0-100% (leak detection only)
Butadiene-1,2 (C4H6)Ethylene (C2H4) 0-100% (leak detection only)
Butene (C4H8)Band C
Cyclopentane (C5H10)Band C
Dichloro-ethane (C2H4Cl2)Band D
AVTUR JP8Band B
Difluoroethane (C2H4F2)Band B
Dimethyl ether (C2H6O)Butane (C4H10)
Ethylene dichloride (EDC)Band D
Ethylene oxide (C2H4O)Band C
Isobutylene (C4H8)
Band B
Iso-hexane (C6H14)
Hexane (C6H14) 0-100% LEL
Methyl ethyl ketone (C4H8O)Butanone (C4H8O) 0-100% LEL
Polypropylene ((C3H6)n)Propylene ((C3H6)n) 0-100% LEL
Styrene (C8H8)Ethylene (C2H4) 0-100% LEL (leak detection only)
Tetrahydrofuran (C4H8O)Band B
Turpentine (C10H16)Band B
Xylene (C8H10)Band C
GasGasGasGas
1,3 Butadiene (C4H6) 100% LELDimethyl disulfideMethyl chloride (CH3Cl)Propane (C3H8) 25% LEL
Acetic acid (C2H4O2)Enflurane (C3H2ClF5O)Methyl fluoride (CH3F)Propane (C3H8) 5% v/v
Acetonitrile (C2H3N)Ethane (C2H6) 10% v/vMethyl mercaptan (CH4S)Pyridine (C5H5N)
Alphamethylstyrene (AMS)Ethanol (C2H6O) 5,000 ppmMethylchloroformate (C2H3ClO2) Sevoflurane ethyl-ether (C4H3F7O)
Aniline (C6H5NH2)Ethylchloroformate (C3H5ClO2)Methylene chloride (CH2Cl2)Sulfuric acid (H2SO4)
Bromopropane (C3H7Br)Ethylene (C2H4) 15,000 ppmMorpholine (C4H9NO)Toluene (C7H8) 10,000 ppm
Butyl isocyanate (C5H9NO)Halothane (C2HBrClF3)N-butane (C4H10) 5% v/vTri-chloro-ethylene (C2HCl3)
Chloroform (CHCl3)Hexane (C6H14) 2,000 ppmPentane (C5H12) 3,000 ppmVCM (C2H3Cl)
Desflurane (C3H2F6O)I-butane (C4H10) 10% v/vPhenol (C6H5OH)Vinylidene
Dichloromethane (CH2Cl2)Isoflurane ether (C3H2ClF5O)Propan (C3H8O) 100% UEG
Dicyclopentadiene (C10H12)Methane (CH4) 40% LELPropane (C3H8) 2,000 ppm

Additional information

Weight 3.53 lbs