Description
Honeywell MIDAS Sensor Cartridge for Phosphine (PH3) 110-1200 ppb
Several Honeywell MIDAS® cartridges can be configured to read a number of different gases based on a common chemical family. Actual details for the sensor detection range are included in the sensor cartridge specification sheet and the MIDAS® technical manual. MIDAS® sensor cartridges can be ordered as part of a Kit with the universal MIDAS® transmitter, or as a replacement part. The detectable range is listed. With the exception of O2 (where ambient concentration is typically 20.9%), the sensors will display zero when no gas is present. All Cartridges with the format MIDAS-E-XXX are supplied with a 2 year (24 month) warranty.
Gas Measured | Phosphine (PH3) | |
---|---|---|
Cartridge Part Number | MIDAS-E-PH3 | 2 year extended warranty |
Sensor Technology | 3 electrode electrochemical cell | |
Measuring Range (ppm) | PH3 | 0 – 1.2 ppm |
Minimum Alarm 1 Set Point | 0.15 ppm | |
Repeatability | < ± 5% of measured value | |
Linearity | < ± 10% of measured value | |
Response Time t62.5 | ≤ 2 seconds | |
Sensor Cartridge Life Expectancy | ≥ 24 months under typical application conditions | |
Operating Temperature | 0°C to +40°C (32°F to 104°F) | |
Effect of Temperature | < ± 0.001ppm / °C (0°C to 20°C) | |
Zero | < ± 0.003 ppm / °C (20°C to 40°C) | |
Sensitivity | < ± 0.6% of measured value / °C | |
Operating Humidity (continuous) | 10 – 90% rH | |
Effect of Humidity | Zero | < 0.0015 ppm / % rH |
Sensitivity | < ± 1% of measured value / % rH | |
Operating Pressure | 90 – 110kPa | |
Effect of Position | No effect in typical application | |
Long Term Drift | Zero | < ± 0.02 ppm / year |
Sensitivity | < ± 10% of measured value / year | |
Calibration Gas | Phosphine (PH3) | |
Challenge Gas (Bump Test) | Phosphine (PH3) | |
Warm Up Time | < 20 minutes | |
Storage Temperature | +5°C to +25°C (+41°F to +77°F) |
Each Midas sensor is potentially cross sensitive to other gases and this may cause a gas reading when exposed to other gases than those originally designated. The table below presents typical readings that will be observed when a new sensor cartridge is exposed to the cross sensitive gas (or a mixture of gases containing the cross sensitive species).
Gas / Vapor | Chemical Formula | Concentration Applied (ppm) | Reading (ppm PH3) |
---|---|---|---|
Ammonia | NH3 | 100 | 1.05 |
Arsine | AsH3 | 1 | 0.68 |
Carbon Monoxide | CO | 2000 | < 0.01 |
Chlorine | Cl2 | 1 | - 0.07 |
Diborane | B2H6 | 1 | 0.45 |
Ethanol | C2H5OH | 2000 | < 0.01 |
Germane | GeH4 | 1 | 0.45 |
Hydrogen | H2 | 5000 | < 0.01 |
Hydrogen Chloride | HCl | 10 | < 0.01 |
Hydrogen Fluoride | HF | 10 | < 0.01 |
Hydrogen Sulfide | H2S | 0.5 | 0.07 |
Iso Propanol | C3H7OH | 2000 | 0 |
Nitrogen Dioxide | NO2 | 8 | - 0.86 |
Silane | SiH4 | 1 | 0.36 |
Sulfur Dioxide | SO2 | 50 | 0.55 |