E3Point without sensor, duct mount, analog, 24 Vac/Vdc

$1,163.00

Description

E3Point

The Honeywell E3Point is capable of detecting the widest range of toxic and combustible gases found in commercial building spaces and outbuildings, including CO, NO2, O2, H2, H2S, CH4 and C3H8. It can be used as a standalone unit with single or dual-gas detection (i.e. using a remote sensor) or deployed as a networkable device (interoperable with BACnet, Modbus or other Building Automation System); E3Point also functions with existing controller-based gas monitoring systems and wired-wireless gas monitoring system components.

E3Point uses Demand Control Ventilation—through relays, Building Automation System (BAS) or controller—to increase energy savings, extend fan life and align with green building best practices. In its network configuration, E3Point also optimizes HVAC, fire/smoke, surveillance and other building systems performance.

Intelligent product design reduces the unit’s cost of ownership while increasing flexibility of application. Smart sensors are pre-calibrated, auto-configure upon set-up and operate continuously on patented Reflex technology which continuously monitors sensor cell condition and alerts user to fault status. The plug-n-play sensor cartridge, user-friendly menu and wiring options simplify installation and maintenance, and reduce the cost of gas monitoring over the life of the unit.
  • Flexible Operation
    • Comes in standalone, standalone with remote (dual gas mode) or network versions
    • Connects to analog or digital systems
    • Works with virtually any BAS including BACnet and Modbus
    • Connects to wired or wireless system (via 301CW wireless controller)
    • Wall or duct mount
    • Factory-calibrated cartridges
  • Cost Effective
    • Saves energy through Demand Control Ventilation (DCV)
    • Simplifies installation/maintenance through plug-n-play sensor
    • Remote sensor option provides dual gas monitoring (standalone version only)
    • Optimizes BAS, fire, ventilation and other security systems
  • Versatile Communications
    • Works through BAS to improve fault diagnostics and collect data on gas concentration levels, sensor condition, etc.
    • Couple with 301C to log data and daisy-chain up to 96 E3Point units
  • Advanced Sensing Technology
    • Detects CO, NO2, O2, H2, H2S, CH4, C3H8
    • Advanced electrochemical (for toxic gases)and catalytic bead (for combustible gases)  sensor performance
    • Uses patented Reflex® and smart cartridge technologies
  • Range of Accessories
    • Factory-calibrated replacement cartridges
    • Power transformer
    • Vandal-resistant steel wire detector guards
    • Tamper-proof screws
    • Horns and strobes
  • Parking Structure
  • Loading Dock Transport Terminal
  • Golf Cart Maintenance
  • Maintenance Garage
  • Hospital/Ambulance Bay
  • Fire/Police Station
  • Car Wash
  • Battery Charging Rooms
  • H2 & Hydrogen Tanks
  • Commercial Kitchen
  • Boiler Rooms
General Technical Specifications
Input power24 VAC nominal17-27 VAC, 50/60 Hz, 0.35 A
24 VDC nominal20-38 VDC
Optional main AC input power120 Vac nominal, ± 10% (with on-board transformer) @ 0.35 A
Relay output2 DPDT relays, 5A @ 250 VAC
Operating environmentCommercial, indoor
Operating temperature rangeH2S, NO2, O2, Combustible-40 to 50°C (-40 to 122°F)
CO-20 to 50°C (-4°F to 122°F)
Available option CO-40 to 50°C (-40 to 122°F)
Operating humidity range15 to 90% RH non-condensing
ResolutionCO1 ppm
O20.1% Vol.
H2S0.1 ppm
NO20.1 ppm
CH4, H2, C3H80.1% LEL
Operating altitudeMaximum 2000m (6562 ft)
Audible alarm>85 dB at 3 m (10 ft)
Display8 character, 2 line LCD
Visual IndicatorsGreen LEDPower
Amber LED 1Alarm/Fault
Amber LED 2Alarm/Fault
EnclosurePolycarbonate
Dimensions (H x W x D)20.56 x 14.90 x 6.72 cm (8.09 x 5.87 x 2.65 in.)
Baud rate9600 (with 301C controller)
CertificationsCSA C22.2 No. 61010-1, UL61010
Detection Specifications
Sensor TypeGasRangeDetection unitAlarm A LevelAlarm A Hysteresis
ElectrochemicalCO0/250ppm25-5
ElectrochemicalO20/25%19.50.5
ElectrochemicalH2S0/50ppm10.0-1.0
ElectrochemicalNO20/10ppm0.7-0.1
Catalytic combustion(CH4)0/100 (5.0% v/v)*% LEL25.0-5.0
Catalytic combustion(H2)0/100 (4.0% v/v)*% LEL25.0-5.0
Catalytic combustion(C3H8)0/100 (2.1% v/v)*% LEL25.0-5.0
* LEL values in accordance to IPCS
GasAlarm B LevelAlarm B HysteresisAlarm C LevelAlarm C HysteresisAccuracy at 25°Display Resolution
CO100-20225-203%1 ppm
O222.0-0.522.5-0.53%0.1%
H2S15.0-1.020.0-5.03%0.1 ppm
NO22.0-1.09.0-1.03%0.1 ppm
(CH4)50.0-5.090.0-5.03%0.1%
(H2)50.0-5.090.0-5.03%0.1%
(C3H8)50.0-5.090.0-5.03%0.1%
Accuracy is the difference in means of 10 calibration measurements at mid-range and 10 measurements at mid-range, at 25°C and 45% RH. This difference is presented as a calculated percent of full scale.

Additional information

Weight 1 lbs
Dimensions 2.7 × 5.9 × 8 in