The Beacon 410A is a highly configurable, microprocessor-based, flexible and easy to use 4 channel gas monitoring controller. It simultaneously displays the gas type, readings, and status for four channels of gas detection. It can monitor any combination of direct connect sensors (LEL, O2, CO2, and toxic gas sensors), as well as any 4-20mA transmitter.
Each channel has up to three fully configurable alarm points. A built-in silenceable audible alarm alerts you to alarm conditions. Each channel also has two dedicated fully configurable relays and there is a bank of common relays as well. The common relays can optionally be configured as additional relays allowing up to 3 alarm relays per channel. Each channel provides a 4-20mA output signal. A digital Modbus interface for remote logging of data via a Modbus network is standard. A Min-Max feature retains high & low peak readings for review at any time.
A fully configurable, high visibility strobe is available as an option. The unit can be powered from 115/220 VAC, or an external 24 VDC source. A trickle charging battery backup feature with battery assembly is also available as an option.
All features and functions of the Beacon 410A are controlled by easy to use menus on the OLED display. All features including form-C relay contacts of the Beacon 410A are built into the unit so you never need to purchase or maintain any “add-on” cards or components.
Simultaneously control up to 4 gas monitoring channels
OLED display of all 4 channels
LEL / O2 / CO2 / toxic direct connect sensors
Accepts any 4-20 mA transmitter, 2 or 3 wire
Up to 3 programmable alarm levels per channel
Up to 3 configurable alarm relays per channel
4-20 mA analog & Modbus digital output standard
115 / 220 VAC or 24 VDC operation
Audible alarm with silence feature
RFI / EMI Resistant
Alarm reset switch
Built in trouble alarm with relay
Weather and corrosion resistant NEMA 4X enclosure
Petrochemical plants
Refineries
Water & wastewater treatment pants
Pulp & paper mills
Gas, telephone, & electric utilities
Parking garages
Manufacturing facilities
Steel
Automotive
HVAC
Physical
Dimensions
Height
12.5”
Width
11”
Depth
6.4”
Enclosure
NEMA 4X non-metallic for indoor and outdoor locations
115 VAC & 220 VAC, or 24 VDC nominal, battery backup option available
Controls
Display PCB Control Switches
UP/YES push button switch
DOWN/NO push button switch
ESCAPE push button switch
ENTER push button switch
External reset switch
On/Off toggle switch
Environmental
Operating Temp
-4°F to 122°F (-20°C to 50°C)
Storage Temp
-4°F to 158°F (-20°C to 70°C)
Relative Humidity
0 – 95% RH (non-condensing)
Enclosure Rating
NEMA-4X enclosure, chemical and weather resistant
Inputs
Direct Wired Sensors
LEL, Oxygen, Carbon Monoxide, Hydrogen Sulfide, and Carbon Dioxide. Remote amp not required for less than 500 feet
4-20 mA Sensors
Accepts any 4-20 mA transmitter (24 VDC, 2 or 3 wire). A wide variety of RKI/Riken sensors are available with 4-20 mA signals. Wiring distances up to 8,000 feet
Sampling Methods
Diffusion and sample draw heads available
Outputs
Relays
Two flexible, programmable Form-C (C, NO, NC) relays per channel, plus five common relays (Fail, Alarm-1, Alarm-2, Alarm-3, Alarm-Any). Common relays may optionally be assigned to function as additional channel alarm relays, providing for up to three alarm relays per channel. 10A contact rating.
4-20 mA
Signal output, 4-20 mA (maximum load impedance 500 ohms), per channel
RS-485
Modbus format RS-485 serial output of all channel data, including gas reading and alarm status.
Display
Four line OLED display
Audible
Built-in audible alarm, 94 dB, mounted on enclosure
Coded output: pulsing = gas alarm, steady = fail
Visual
Alarm LEDs (on Display PCB)
Alarm 1, yellow
Alarm 2, orange
Alarm 3, red
Fail, yellow
Green Pilot LED to indicate AC power connected (on Display PCB)
An optional 24 VDC NEMA 4X strobe mounted to top of case.
Warranty
One year materials and workmanship
Partial List Of Detectable Gases
Many other gases or ranges available. Contact us for gases or ranges not listed.