Description
Analog Input Module 4-20mA (4 channels per module)
The Touchpoint Pro Input/Output modules can be combined up to a maximum of 16 input
modules (64 channels) and 32 output modules (128 channels). Modules can be located in
any Touchpoint Pro enclosure. Power distribution is via the Communication/Power Rail.
Touchpoint Pro Analog Input Module mA
Touchpoint Pro Analog Input Module mA Terminal Identification
Analog Input Module mA | ||
---|---|---|
Description | 4-channel 4-20 mA Analog Input Module with 2 or 3 wire interface to detector | |
Sensor Configuration | 4 x 2-wire or 3-wire (current sourced from detector) | |
Signal Measurement Range | 0-25 mA | |
Supply Voltage (Vs) | 24 Vdc (18-32 Vdc) | |
Field Device Supply Voltage | Supply Voltage (Vs) – 0.7 V | |
Single Channel Field Device Supply Current | Maximum 1 A | |
Total Field Device Supply Current | Total Maximum current: | 2 A at 65°C ambient |
Total Maximum current: | 4 A at 55°C ambient | |
Power Consumption | 0.8 W (Excluding sensor supply) | |
Power Dissipation | Maximum 3.7 W, at 4 A total field device load | |
Maximum 2.1 W, at 2 A total field device load | ||
Sense Resistance | 101 Ω | |
Connector Coding | Analog Input Module connectors (TB1-TB4) are coded with coding keys to avoid mis-wiring | |
DIN Rail connector (Module Supply and Communication) | Maximum Current: | 4.04 A (18-32 Vdc) |
Terminal Identification | Label | Channel | Field Device |
---|---|---|---|
1 | +V | Input 1 | +24 Vdc |
2 | SIG | 4-20 mA signal | |
3 | -V | 0 Vdc | |
4 | +V | Input 2 | +24 Vdc |
5 | SIG | 4-20 mA signal | |
6 | -V | 0 Vdc | |
7 | +V | Input 3 | +24 Vdc |
8 | SIG | 4-20 mA signal | |
9 | -V | 0 Vdc | |
10 | +V | Input 4 | +24 Vdc |
11 | SIG | 4-20 mA signal | |
12 | -V | 0 Vdc |