Use the Touchpoint Pro Part Number and Pricing Configurator design to build flexible 19’’ Rack Control Systems.
19’’ 5U Rack Controller Enclosure |
Part Number | TPPR-V-0602 |
Material | Mild Steel |
Earthing Points | M8 (main grounding); other M6 |
Dimensions (H x W x D) | 19 in x 8.74 in x 4.33 in (483 mm x 222 mm x 110 mm) |
Weight | 22 lbs (10 kg) |
19’’ 5U Rack Remote Unit Enclosure |
Part Number | TPPR-V-0612 |
Material | Mild Steel |
Earthing Points | M8 (main grounding); other M6 |
Dimensions (H x W x D) | 19 in. x 8.74 in. x 4.33 in. (483 mm x 222 mm x 110 mm) |
Weight | 19.84 lbs (9 kg) |
Ring Coupling Module
Ring Coupling Module |
Communication / Power Rail |
Description | 5, 7, 9 or 10-way Communication / Power Rail consists of 1 DIN Rail, 1 Ring Coupling Module (RCM), and a 5, 7, 9 or 10-way Backplane |
DIN Rail |
Total Width | 16.93 in. (430 mm) |
Type | TS-35/15 |
Ring Coupling Module (RCM) |
Description | Module for connection of DIN Rail mounted I/O modules to Ring Network |
Electrical Connection | 2 x Ring Network TX / RX Driver Pairs (Each 2-Wire plus Drain) |
Supply Voltage | 24 Vdc (18-32 Vdc) |
Power Consumption | Maximum 1 W |
Power Dissipation | Maximum 1 W |
Ring Network Cable | Minimum 2 x 2 x 1 mm2 twisted pair, plus Drain and Overall Screen |
Operating Temperature | -40°C to +65°C |
Storage Temperature | -40°C to +65°C |
Environmental Protection Class | Pollution Degree 2 (indoor sheltered) |
Connector Coding | Ring cable connectors (TB1-TB4) are coded with coding keys to avoid mis-wiring. |
DIN Rail connector (Module Supply and Communication) | Maximum Current: 60 mA (18-32 Vdc) |
Backplane |
Description | 5, 7, 9 and 10 I/O slot (excluding first slot reserved for RCM) backplane PCB for providing power and Ring Network connections to the RCM and I/O modules |
Electrical Connection | 2-wire (+V and –V) at Power Supply Input for 5, 7, 9 I/O Slot Backplane |
2 x 2-wire (+V and –V) at Power Supply Input for 10 I/O Slot Backplane |
10-pin backplane connector for connection to RCM and I/O Modules |
Maximum Wire Size | 6 mm2 |
Supply Voltage | 24 Vdc (18-32 Vdc) |
Backplane current Rating | Maximum 20 A |
Power Supply Connector Rating | Maximum 32 V, 41 A |
Backplane connector | Maximum 32 V, 4.04 A |
Environmental Protection Class | Pollution Degree 2 (indoor sheltered) |
Operating Temperature | -40°C to +65°C |
Storage Temperature | -40°C to +65°C |
Touchpoint Pro Communication/Power Rail Terminal Identification
Terminal Identification | Label | Channel |
1 | + | Ring A In |
2 | Drain |
3 | - |
4 | + | Ring B Out |
5 | Drain |
6 | - |
7 | + | Ring B in |
8 | Drain |
9 | - |
10 | + | Ring A Out |
11 | Drain |
12 | - |
Touchpoint Pro Power Supply Units
Power Supply Units |
Power Supply | 120 W (5A) | 240 W (10A) | 480 W (20A) |
Input Voltage Range | 85 - 264 Vac; 88 – 360 Vdc |
Input Frequency Range | 50 - 60 Hz ±6% |
Input AC current | 1.10 A at 120 Vac | 2.22 A at 120 Vac | 4.56 A at 120 Vac |
0.62 A at 230 Vac | 1.22 A at 230 Vac | 2.48 A at 230 Vac |
Output Voltage | 24 Vdc (Adjustable 24 - 28 Vdc) |
DC OK Relay contact ratings (max.) | 60 Vdc 0.3 A / 30 Vdc 1 A / 30 Vac 0.5 A resistive load |
Protection | Short Circuit, Overload (current limiting), No load, Over Voltage, Over Temperature |
Dimensions (W x H x D) | 1.57 in. x 4.88 in. x 4.61 in. (40 mm x 124 mm x 117 mm) | 2.36 in. x 4.88 in. x 4.61 in. (60 mm x 124 mm x 117 mm) | 3.23 in. x 4.88 in. x 5 in. (82 mm x 124 mm x 127 mm) |
Operating Temperature | -25 °C to +70 °C (-13 °F to 158 °F) |
Derating (60 °C to 70 °C) | 3 W/°C | 6 W/°C | 12 W/°C |
Storage Conditions | -40 to +85 °C (-40 °F to 185 °F), 5% to 95% RH |
Operating Humidity | 5% to 95% RH (non-condensing) |
Touchpoint Pro 120 W 24 Vdc Power Supply Unit
Label | Purpose |
N | AC Supply Neutral |
L | AC Supply Live |
| Earth |
+ | DC Output +V |
+ | DC Output +V |
- | DC Output -V |
- | DC Output -V |
DC OK | Relay Contact |
DC OK | Relay Contact |
Touchpoint Pro 240 & 480 W 24 Vdc Power Supply Unit
Label | Purpose |
N | AC Supply Neutral |
L | AC Supply Live |
| Earth |
+ | DC Output +V |
+ | DC Output +V |
- | DC Output -V |
- | DC Output -V |
DC OK | Relay Contact |
DC OK | Relay Contact |
Touchpoint Pro Uninterruptible Power Supply Module (UPS)
Uninterruptible Power Supply Module (UPS) |
Description | 23.3 Vdc - 30 Vdc |
Input Current | 70 mA typical internal current consumption |
Current consumption for battery charging in constant current mode at 24V input |
1.7 A typical at battery selector position <10Ah |
3.4 A typical at battery selector position >10Ah |
Output Voltage | 24 Vdc (nominal) in Normal Operation |
Adjustable in Battery Operation |
Output Current | max. 25 A in Normal Operations |
min. 20 A in Battery Operation |
Allowed Batteries | 2 x 12 V |
3.9 Ah – 130 Ah |
VRLA lead acid type |
Dimensions (W x H x D) | 1.81 in. x 4.88 in. x 5 in. (46 mm x 124 mm x 127 mm) |
Operating Temperature | -40°C to +70°C |
Derating 60°C to 70°C | 0.5 A/ºC |
Storage Conditions | -40°C to +85°C, 5% to 95% RH |
Operating Humidity | 5% to 95% RH (non-condensing) |
Touchpoint Pro Backup Battery
Backup Battery |
Description | 24 V sealed lead acid battery, 12 Ah or 27 Ah options |
Electrical Connection | 2 x 12 Vdc batteries in series |
Dimensions (W x H x D) | 15.6 in. x 11.8 in. x 8.5 in. (395 mm x 300 mm x 215 mm) |
Weight | 12 Ah version: 34.6 lbs (15.7 kg) |
27 Ah version: 55.1 lbs (25 kg) |
Operating Temperature | -20°C to +45°C |
Operating Humidity | 10% to 90% RH non condensing |
Storage Conditions | -20°C to +40°C, 10% to 90% RH |
Storage Lifetime without re-charge | 18 months at <5°C, 6 months at 25°C, 3 months at 30°C, 2 months at 40°C |
Ingress Protection | IP20, NEMA Code 1 |
Input Voltage (charging) | 25 Vdc to 28 Vdc (UPS Supervised) |
Output Voltage (when supplying) | 20 Vdc to 28 Vdc (dependent on charge level) |
Maximum Input Current | 3 A |
Maximum Output Current | 20 A |
Environmental Protection Class | Pollution Degree 2 (indoor sheltered) |
Battery Type | FIAMM 12 V 12 Ah FG21202 or FIAMM 12 V 27 Ah FG22703 |
Fuse Type (inline) | Bussman 20 A Fast Acting 1.25” Type ABC-20-R |
Current Limit Protection | Double pole circuit breaker / Isolator, 20 A |
Maximum Altitude | 2000 m |
Touchpoint Pro UPS Connections
The UPS connections are as follows: |
Terminal Identification | Label | Purpose |
Input DC 24 V | + | DC Supply +V |
- | DC Supply -V |
- | DC Supply -V (spare) |
Output DC 24 V 20 A | + | +V Supply to Touchpoint Pro system |
- | -V Supply to Touchpoint Pro system |
Battery | + | Battery + |
- | Battery - |
Touchpoint Pro UPS Status Relays
The UPS is equipped with status relays as follows: |
Terminal Identification | Label | Purpose |
1 | Ready | Contact is closed when both batteries are charged, all OK |
2 |
3 | Buffering | Contact is closed when UPS has switched to battery power |
4 |
5 | Replace Battery | Contact is closed when a battery quality fault is detected |
6 |
7 | Inhibit | DO NOT USE |
8 |
Touchpoint Pro Analog Input Module mA
Analog Input Module mA |
Description | 4-channel 4-20 mA Analog Input Module with 2 or 3 wire interface to detector |
Sensor Configuration | 4 x 2-wire or 3-wire (current sourced from detector) |
Signal Measurement Range | 0-25 mA |
Supply Voltage (Vs) | 24 Vdc (18-32 Vdc) |
Field Device Supply Voltage | Supply Voltage (Vs) – 0.7 V |
Single Channel Field Device Supply Current | Maximum 1 A |
Total Field Device Supply Current | Total Maximum current: | 2 A at 65°C ambient |
Total Maximum current: | 4 A at 55°C ambient |
Power Consumption | 0.8 W (Excluding sensor supply) |
Power Dissipation | Maximum 3.7 W, at 4 A total field device load |
Maximum 2.1 W, at 2 A total field device load |
Sense Resistance | 101 Ω |
Connector Coding | Analog Input Module connectors (TB1-TB4) are coded with coding keys to avoid mis-wiring |
DIN Rail connector (Module Supply and Communication) | Maximum Current: | 4.04 A (18-32 Vdc) |
Touchpoint Pro Analog Input Module mA Terminal Identification
Terminal Identification | Label | Channel | Field Device |
1 | +V | Input 1 | +24 Vdc |
2 | SIG | 4-20 mA signal |
3 | -V | 0 Vdc |
4 | +V | Input 2 | +24 Vdc |
5 | SIG | 4-20 mA signal |
6 | -V | 0 Vdc |
7 | +V | Input 3 | +24 Vdc |
8 | SIG | 4-20 mA signal |
9 | -V | 0 Vdc |
10 | +V | Input 4 | +24 Vdc |
11 | SIG | 4-20 mA signal |
12 | -V | 0 Vdc |
Touchpoint Pro Analog Input Module mV
Analog Input Module mV |
Description | 4-channel Analog Input Module for Catalytic Bridge sensors |
Electrical Connection | 4 x 3-wire mV-Bridge |
Supply Voltage | 24 Vdc (18-32 Vdc) |
Sensor Drive method | Constant current |
Programmable Current Range | 180-360 mA |
Maximum Loop Resistance | Total Maximum loop resistance: | 40 Ω at 200 mA (including Sensor) |
Total Maximum loop resistance: | 27 Ω at 360 mA (including Sensor) |
Input Range | ±15 mV to ±600 mV |
Power Consumption | Maximum 1.2 W (Excluding Sensors) |
Power Dissipation | Maximum 3.5 W |
Connector Coding | Analog Input Module connectors (TB1-TB4) are coded with coding keys to avoid mis-wiring |
DIN Rail connector (Module Supply and Communication) | Maximum Current: | 1.1 A (18-32 Vdc) |
Touchpoint Pro Analog Input Module mV Terminal Identification
Terminal Identification | Label | Channel | Field Device |
1 | S | Input 1 | Sensitive (+) |
2 | 01 | Signal |
3 | NS | Non-sensitive (-) |
4 | S | Input 2 | Sensitive (+) |
5 | 01 | Signal |
6 | NS | Non-sensitive (-) |
7 | S | Input 3 | Sensitive (+) |
8 | 01 | Signal |
9 | NS | Non-sensitive (-) |
10 | S | Input 4 | Sensitive (+) |
11 | 01 | Signal |
12 | NS | Non-sensitive (-) |
Touchpoint Pro Digital Input Module
Digital Input Module |
Description | 4-Channel Digital Input Module for switched input devices |
Electrical Connection | 4 x 2-wire Switch Inputs |
Supply Voltage | 24 Vdc (18-32 Vdc) |
Power Consumption | 1 W maximum (no inputs connected) |
Power Dissipation | 2.8 W maximum |
Field Terminals (TB1-TB4) Ratings | Maximum current of 14 mA through switched input device at 18-32 Vdc |
EOL (End Of Line) Resistance | 10 kΩ, 0.25 W, ±1% |
INL (In-Line) Resistance | 2.7 kΩ, 0.25 W, ±1% |
Switch Input Device supply
Voltage (Vs) | Minimum | 15 V |
Maximum | 32 V |
Switch Input Device supply
Current (Is) | Minimum | 5 mA for Supervised OC/SC Switch ON condition |
Maximum | 14 mA for Unsupervised Switch ON condition |
Connector Coding | Digital Input Module connectors (TB1-TB4) are coded with coding keys to avoid mis-wiring |
DIN Rail connector (Module Supply and Communication) | Maximum Current: | 95 mA (18-32 Vdc) |
Touchpoint Pro Digital Input Module Terminal Identification
Terminal Identification | Label | Channel |
1 | + | Input 1 |
2 | |
3 | - |
4 | + | Input 2 |
5 | |
6 | - |
7 | + | Input 3 |
8 | |
9 | - |
10 | + | Input 4 |
11 | |
12 | - |
Touchpoint Pro Relay Output Module
Relay Output Module |
Description | 4-channel Relay Output Module incorporating 4 single pole change over (SPCO) relays and 24 Vdc Auxiliary Power Output |
Electrical Connection | 4 x SPCO Relay Terminals (TB1 to TB4) |
4 x 2-wire Auxiliary Output Terminals (TB5 to TB8) |
Supply Voltage (Vs) | 24 Vdc (18-32 Vdc) |
Auxiliary Supply Voltage | Supply Voltage (Vs) – 0.7 V |
Auxiliary Supply Current | Maximum 1.5 A |
Power Consumption | Maximum 1.5 W (excluding auxiliary power consumption) |
Power Dissipation | Maximum 2.3 W |
Relay Contacts (TB1-TB4) | Maximum 5 A through one relay contact at 250 Vac / 30 Vdc (non-inductive) |
Maximum 8 A total through all four relay contacts at 250 Vac / 30 Vdc (non-inductive) |
Minimum 12 Vdc, 10 mA |
Connector Coding | Relay output connectors (TB1-TB4) and auxiliary output connectors (TB5-TB8) are coded with coding keys to avoid mis-wiring. |
The relay output connectors (TB1-TB4) are colored black to identify them for AC supply wiring |
DIN Rail connector (Module Supply and Communication) | Maximum Current: | 1.62 A (18-32 Vdc) |
Touchpoint Pro Relay Output Module Terminal Identification
Terminal Identification | Label | Channel |
1 | NO | Relay 1 |
2 | NC |
3 | C |
4 | NO | Relay 2 |
5 | NC |
6 | C |
7 | NO | Relay 3 |
8 | NC |
9 | C |
10 | NO | Relay 4 |
11 | NC |
12 | C |
13 | | V Aux 1 |
14 | +V |
15 | -V |
16 | | V Aux 2 |
17 | +V |
18 | -V |
19 | | V Aux 3 |
20 | +V |
21 | -V |
22 | | V Aux 4 |
23 | +V |
24 | -V |