Beacon 410A

Beacon 410A Category

The Beacon 410A is a highly configurable, microprocessor-based, flexible and easy to use 4 channel gas monitoring controller. It simultaneously displays the gas type, readings, and status for four channels of gas detection. It can monitor any combination of direct connect sensors (LEL, O2, CO2, and toxic gas sensors), as well as any 4-20mA transmitter.



Each channel has up to three fully configurable alarm points. A built-in silenceable audible alarm alerts you to alarm conditions. Each channel also has two dedicated fully configurable relays and there is a bank of common relays as well. The common relays can optionally be configured as additional relays allowing up to 3 alarm relays per channel. Each channel provides a 4-20mA output signal. A digital Modbus interface for remote logging of data via a Modbus network is standard. A Min-Max feature retains high & low peak readings for review at any time.

A fully configurable, high visibility strobe is available as an option. The unit can be powered from 115/220 VAC, or an external 24 VDC source. A trickle charging battery backup feature with battery assembly is also available as an option.

All features and functions of the Beacon 410A are controlled by easy to use menus on the OLED display. All features including form-C relay contacts of the Beacon 410A are built into the unit so you never need to purchase or maintain any “add-on” cards or components.
  • Simultaneously control up to 4 gas monitoring channels
  • OLED display of all 4 channels
  • LEL / O2 / CO2 / toxic direct connect sensors
  • Accepts any 4-20 mA transmitter, 2 or 3 wire
  • Up to 3 programmable alarm levels per channel
  • Up to 3 configurable alarm relays per channel
  • 4-20 mA analog & Modbus digital output standard
  • 115 / 220 VAC or 24 VDC operation
  • Audible alarm with silence feature
  • RFI / EMI Resistant
  • Alarm reset switch
  • Built in trouble alarm with relay
  • Weather and corrosion resistant NEMA 4X enclosure
  • Petrochemical plants
  • Refineries
  • Water & wastewater treatment pants
  • Pulp & paper mills
  • Gas, telephone, & electric utilities
  • Parking garages
  • Manufacturing facilities
  • Steel
  • Automotive
  • HVAC
Physical
DimensionsHeight12.5”
Width11”
Depth6.4”
EnclosureNEMA 4X non-metallic for indoor and outdoor locations
Conduit Connection3/4” NPT conduit hubs, 4 provided, for sensor, power, & relay wiring
Wiring TerminationScrew type terminal block, 14 gauge max
Power115 VAC & 220 VAC, or 24 VDC nominal, battery backup option available
ControlsDisplay PCB Control SwitchesUP/YES push button switch
DOWN/NO push button switch
ESCAPE push button switch
ENTER push button switch
External reset switch
On/Off toggle switch
Environmental
Operating Temp-4°F to 122°F (-20°C to 50°C)
Storage Temp-4°F to 158°F (-20°C to 70°C)
Relative Humidity0 – 95% RH (non-condensing)
Enclosure Rating NEMA-4X enclosure, chemical and weather resistant
InputsDirect Wired SensorsLEL, Oxygen, Carbon Monoxide, Hydrogen Sulfide, and Carbon Dioxide. Remote amp not required for less than 500 feet
4-20 mA SensorsAccepts any 4-20 mA transmitter (24 VDC, 2 or 3 wire). A wide variety of RKI/Riken sensors are available with 4-20 mA signals. Wiring distances up to 8,000 feet
Sampling MethodsDiffusion and sample draw heads available
Outputs
RelaysTwo flexible, programmable Form-C (C, NO, NC) relays per channel, plus five common relays (Fail, Alarm-1, Alarm-2, Alarm-3, Alarm-Any). Common relays may optionally be assigned to function as additional channel alarm relays, providing for up to three alarm relays per channel. 10A contact rating.
4-20 mASignal output, 4-20 mA (maximum load impedance 500 ohms), per channel
RS-485Modbus format RS-485 serial output of all channel data, including gas reading and alarm status.
DisplayFour line OLED display
AudibleBuilt-in audible alarm, 94 dB, mounted on enclosure
Coded output: pulsing = gas alarm, steady = fail
VisualAlarm LEDs (on Display PCB)Alarm 1, yellow
Alarm 2, orange
Alarm 3, red
Fail, yellow
Green Pilot LED to indicate AC power connected (on Display PCB)
An optional 24 VDC NEMA 4X strobe mounted to top of case.
WarrantyOne year materials and workmanship
Partial List Of Detectable GasesMany other gases or ranges available. Contact us for gases or ranges not listed.
Ammonia (NH3)0 – 75.0 ppm
Arsine (AsH3)0 – 0.20 ppm
Boron Trichloride (BCl3)0 – 15.0 ppm
Carbon Dioxide (CO2)0 – 1.0 %
Carbon Monoxide (CO)0 – 300 ppm
Chlorine (Cl2)0 – 3.0 ppm
Chlorine Dioxide (ClO2)0 – 1.00 ppm
Chlorine Trifluoride (ClF3)0 – 1.00 ppm
Combustibles0 -100% LEL
Diborane (B2H6)0 – 30.0 ppm
Fluorine (F2)0 – 6.0 ppm
Hydrogen (H2)0 – 2000 ppm
Hydrogen Chloride (HCl)0 – 15.0 ppm
Hydrogen Fluoride (HF)0 – 9.0 ppm
Hydrogen Sulfide (H2S)0 -100.0 ppm
Nitric Oxide (NO)0 -100.0 ppm
Nitrogen Dioxide (NO2)0 – 15.0 ppm
Nitrogen Trifluoride (NF3)0 – 30.0 ppm
Oxygen (O2)0 – 25.0%
Ozone (O3)0 – 1.0 ppm
Phosphine (PH3)0 – 1.0 ppm
Silane (SiH4)0 – 15.0 ppm
Sulfur Dioxide (SO2)0 – 30.0 ppm
TEOS (Si(OC2H5)4)0 -15/30 ppm

Showing all 4 results