Touchpoint Plus


Honeywell Touchpoint Plus

The Honeywell Touchpoint Plus is an easily configurable, wall mounted control system that supports up to sixteen channels of gas detection. Its intuitive user interface and modular approach enables you to take control of your safety system and configure it to meet your needs for a wide range of applications.

Designed to work across multiple industries, Touchpoint Plus' modular architecture enables you to customize your system to meet your specific application requirements.
Large touchscreen LCD

Built around its intuitive, ergonomic touchscreen, Touchpoint Plus is designed for ease. From here operators can configure, operate and maintain their gas detection system simply and efficiently by simply touching the screen. The multilingual interface simplifies operation, reducing training requirements and costs. Real-time data is presented in an easy to navigate menu system, whilst historical data can be downloaded to monitor developing threats.

At a glance system visibility

When fast and informed decisions need to be made, Touchpoint Plus' full color traffic light style status indicators provide clarity from a distance allowing operators to see system status at-a-glance and make time critical decisions easily.

Unique industrial design

Made of high-impact polymer plastic, Touchpoint Plus is versatile and durable. It is dust-proof, water-proof and has been tested to withstand the toughest environments in which our customers operate - indoors and out. Touchpoint Plus can be directly wall mounted, or for an easier 1-man installation there is an optional mounting plate. Behind the hinged front cover there is plenty of space for wiring and a unique tiered terminal arrangement for easy access. Cable entries are pre-drilled and sealed ready to use, further reducing installation time and cost.

Honeywell Analytics' full system solution

Touchpoint Plus provides a reliable safety solution for small scale gas detection systems across a wide range of applications and industries. As the heart of your gas detection system, Touchpoint Plus is designed to work with Honeywell’s industry leading gas detectors and drive actuators, audible and visual alarms to provide a complete end-to-end, highly configurable safety solution.

Additional Features and Benefits

• Quick and easy setup and use

• Intuitive touchscreen user interface

• Traffic light style status at a glance

• Ergonomic industrial design

• Suited to a wide range of industries
General Specification
CapacityUp to 8 channels with base unit, up to 16 channels with expansion unit
Type of inputs2 or 3 wires, mA, mV, max. 15W per channel, max 40W total (with dedicated A/V drive) / 68W total (without dedicated A/V drive)
Size (wall-mounted version)16.8” x 11.8” x 6.1” (426 mm × 300 mm × 156 mm)
Housing MaterialPolycarbonate ABS
WeightMax 8.5 kg (18.7 lb), max 17 kg (37.4 lb) with expansion unit
User Interface (UI) - Controller Only
Display7’’ color LCD touchscreen
Graphic User Interface
Visual indicators3 LEDs for master indicators, LED for each channel
Green: Normal
Yellow: Fault; Inhibit
Red: Alarm
Audible alarm≥ 70dB @ 1m
ButtonCommon for reset/mute operation
LanguageEnglish, French, German, Italian, Dutch, Spanish, Portuguese, Russian, Chinese
Power Supply
Power AC110/220 VAC, 50-60Hz Manual switching
Power DC18 to 32 VDC (+/-10%) Typical 24 VDC
Power consumptionMax 105W (including detector and external devices), max 210W with expansion unit
Environmental
Operating-10 °C to +55 °C (14 °F to +131 °F) continuous, up to 95% RH (noncondensing), IP65, and NEMA 4X
StorageInstrument -25°C to +60°C. (-13°F to +140°F), up to 95% RH (non-condensing)
Available I/O Modules
4~20mA input2 or 3 wire, 2/4/8 channel modules, 10/12/16 with expansion unit
mV inputCatalytic type flammable gas detectors (Honeywell models). 2/4/8 channel modules, 10/12/16 with expansion unit
Dual Input2 channel mA + 2 channel mV module or 4 channel mA + 4 channel mV module
Relay output12 or 24 relay outputs, NO/C/NC changeover, 1.7A@30VDC/250VAC, user configurable - energized/de-energized, latching/non latching, time delay
4~20mA output4 or 8 isolated repeated mA outputs, 0-22mA, 0-100%FSD = 4-20mA
Common inputsRemote reset, remote inhibit
Common outputsFour powered A/V outputs for alarms and fault, three common alarm outputs
Approvals
Electromagnetic Compatibility and Electrical SafetyEMC/RFI (EN 50270:2015)
LVD (EN 61010-1:2010)
CSA-C22.2 No. 61010-1-04
UL 61010-1 (3rd Edition) and 508
PerformanceEN 50271:2010; EN 60079-29-1:2016; EN 45544-1 /-2 /-3:2015; EN 50104:2010 C22.2 No. 152-M1984, ISA 12.13.01
Safety IntegrityIEC 61508:2010 Ed.2 SIL2, EN 50271:2010
Hazardous LocationClass I, Division 2, Group A, B, C and D or non-hazardous only
MarineMED (Item No.: 3.54)
Others
Backup battery22.2V Lithium Ion Battery, 2600mAh capacity (>30 minutes for typical system)
Data loggingConfiguration, logged events and data
CommunicationMODBUS TCP, WEB monitoring and MODBUS RTU