Description
Battery Backup Enclosure (for two batteries – 12 Ah size or 27 Ah size)
Battery Backup Enclosure (for two batteries - 12 Ah size or 27 Ah size) for Touchpoint Pro, charged by UPS module.
Touchpoint Pro Backup Battery
Touchpoint Pro Uninterruptible Power Supply Module
Touchpoint Pro UPS Connections
Touchpoint Pro UPS Status Relays
Backup Battery | |
---|---|
Description | 24 V sealed lead acid battery, 12 Ah or 27 Ah options |
Electrical Connection | 2 x 12 Vdc batteries in series |
Dimensions (W x H x D) | 15.6 in. x 11.8 in. x 8.5 in. (395 mm x 300 mm x 215 mm) |
Weight | 12 Ah version: 34.6 lbs (15.7 kg) |
27 Ah version: 55.1 lbs (25 kg) | |
Operating Temperature | -20°C to +45°C |
Operating Humidity | 10% to 90% RH non condensing |
Storage Conditions | -20°C to +40°C, 10% to 90% RH |
Storage Lifetime without re-charge | 18 months at <5°C, 6 months at 25°C, 3 months at 30°C, 2 months at 40°C |
Ingress Protection | IP20, NEMA Code 1 |
Input Voltage (charging) | 25 Vdc to 28 Vdc (UPS Supervised) |
Output Voltage (when supplying) | 20 Vdc to 28 Vdc (dependent on charge level) |
Maximum Input Current | 3 A |
Maximum Output Current | 20 A |
Environmental Protection Class | Pollution Degree 2 (indoor sheltered) |
Battery Type | FIAMM 12 V 12 Ah FG21202 or FIAMM 12 V 27 Ah FG22703 |
Fuse Type (inline) | Bussman 20 A Fast Acting 1.25” Type ABC-20-R |
Current Limit Protection | Double pole circuit breaker / Isolator, 20 A |
Maximum Altitude | 2000 m |
Uninterruptible Power Supply Module (UPS) | |
---|---|
Description | 23.3 Vdc - 30 Vdc |
Input Current | 70 mA typical internal current consumption |
Current consumption for battery charging in constant current mode at 24V input | |
1.7 A typical at battery selector position <10Ah | |
3.4 A typical at battery selector position >10Ah | |
Output Voltage | 24 Vdc (nominal) in Normal Operation |
Adjustable in Battery Operation | |
Output Current | max. 25 A in Normal Operations |
min. 20 A in Battery Operation | |
Allowed Batteries | 2 x 12 V |
3.9 Ah – 130 Ah | |
VRLA lead acid type | |
Dimensions (W x H x D) | 1.81 in. x 4.88 in. x 5 in. (46 mm x 124 mm x 127 mm) |
Operating Temperature | -40°C to +70°C |
Derating 60°C to 70°C | 0.5 A/ºC |
Storage Conditions | -40°C to +85°C, 5% to 95% RH |
Operating Humidity | 5% to 95% RH (non-condensing) |
The UPS connections are as follows: | ||
---|---|---|
Terminal Identification | Label | Purpose |
Input DC 24 V | + | DC Supply +V |
- | DC Supply -V | |
- | DC Supply -V (spare) | |
Output DC 24 V 20 A | + | +V Supply to Touchpoint Pro system |
- | -V Supply to Touchpoint Pro system | |
Battery | + | Battery + |
- | Battery - |
The UPS is equipped with status relays as follows: | ||
---|---|---|
Terminal Identification | Label | Purpose |
1 | Ready | Contact is closed when both batteries are charged, all OK |
2 | ||
3 | Buffering | Contact is closed when UPS has switched to battery power |
4 | ||
5 | Replace Battery | Contact is closed when a battery quality fault is detected |
6 | ||
7 | Inhibit | DO NOT USE |
8 |