TPPR-M 10 Way Communication/Power Rail

$1,098.20

Customer Setup

For Custom, select the same amount of "Custom" options as you have I/O Modules, as the price is applied per each I/O module.

Optional Terminal Block

For Module, select the same amount of "Module" options as you have I/O Modules, as the price is applied per each I/O module.

Product price: $1,098.20
Total options:
Order total:

Description

Consists of a DIN Rail blank panel, 1 Ring Coupling Module and 10 Backplanes

Touchpoint Pro Communication/Power Rail

Power distribution for the Touchpoint Pro is via the Communication/Power Rail.

The Touchpoint Pro Communication/Power Rail provides direct power and network connection to the Input/Output modules, minimizing the wiring required. There is a single connection for the 24 Vdc supply and the network cables connect to the Ring Coupling module, which handles the communication between the modules and the central controller.

Depending on the power supply option chosen and the enclosure version, the Communication/Power Rail has space for 5, 7, 9, or 10 Input/Output modules. The Ring Network is the communication link between all Input/Output modules in a Touchpoint Pro system and the central controller. The Ring Network is the only connection required between a local Touchpoint Pro unit (containing the central controller and user interface) and remote Touchpoint Pro units. The Ring Network is implemented for redundancy as two loops transmitting in opposite directions (Ring A and Ring B). The network is self-healing since each module only communicates with the one next to it. If a module fails, the modules after it continue to transmit data in the direction away from the failed module, while the ones before it transmit in the other direction. Thus the Touchpoint Pro system can immediately detect and locate a failed module, without affecting the availability of the rest of the system.

The Touchpoint Pro Input/Output plug-in modules can be combined up to a maximum of 16 input modules (64 channels) and 32 output modules (128 channels). Modules can be located in any Touchpoint Pro enclosure and Touchpoint Pro accepts analog, digital and relay modules, making it one of the most flexible controllers available.
Touchpoint Pro Communication / Power Rail Terminal Identification
Terminal IdentificationLabelChannel
1+Ring A In
2Drain
3-
4+Ring B Out
5Drain
6-
7+Ring B in
8Drain
9-
10+Ring A Out
11Drain
12-
Touchpoint Pro Ring Coupling Module
Ring Coupling Module
Communication / Power Rail
Description5, 7, 9 or 10-way Communication / Power Rail consists of 1 DIN Rail, 1 Ring Coupling Module (RCM), and a 5, 7, 9 or 10-way Backplane
DIN Rail
Total Width16.93 in. (430 mm)
TypeTS-35/15
Ring Coupling Module (RCM)
DescriptionModule for connection of DIN Rail mounted I/O modules to Ring Network
Electrical Connection2 x Ring Network TX / RX Driver Pairs (Each 2-Wire plus Drain)
Supply Voltage24 Vdc (18-32 Vdc)
Power ConsumptionMaximum 1 W
Power DissipationMaximum 1 W
Ring Network CableMinimum 2 x 2 x 1 mm2 twisted pair, plus Drain and Overall Screen
Operating Temperature-40°C to +65°C
Storage Temperature-40°C to +65°C
Environmental Protection ClassPollution Degree 2 (indoor sheltered)
Connector CodingRing cable connectors (TB1-TB4) are coded with coding keys to avoid mis-wiring.
DIN Rail connector (Module Supply and Communication)Maximum Current: 60 mA (18-32 Vdc)
Backplane
Description5, 7, 9 and 10 I/O slot (excluding first slot reserved for RCM) backplane PCB for providing power and Ring Network connections to the RCM and I/O modules
Electrical Connection2-wire (+V and –V) at Power Supply Input for 5, 7, 9 I/O Slot Backplane
2 x 2-wire (+V and –V) at Power Supply Input for 10 I/O Slot Backplane
10-pin backplane connector for connection to RCM and I/O Modules
Maximum Wire Size6 mm2
Supply Voltage24 Vdc (18-32 Vdc)
Backplane current RatingMaximum 20 A
Power Supply Connector RatingMaximum 32 V, 41 A
Backplane connectorMaximum 32 V, 4.04 A
Environmental Protection ClassPollution Degree 2 (indoor sheltered)
Operating Temperature-40°C to +65°C
Storage Temperature-40°C to +65°C
Touchpoint Pro Input/Output Modules Common Specifications
Input/Output Modules Common Specifications
Dimensions (W x H x D)1.38 in. x 3.92 in. x 4.51 in. (35.0 mm x 99.5 mm x 114.5 mm)
Installation5, 7, 9 or 10-way Communication / Power Rail
Maximum Wire Size2.5 mm2
IP RatingIP20
EMCEN 50270
Power Supply18-32 Vdc (24 Vdc nominal)
DIN Rail CompatibilityTS-35 / 15
Casing MaterialPolyamide PA 6.6 V0 (UL94)
Operating Temperature Range-40°C to 65°C
Storage Conditions-40°C to 65°C
Operating Humidity Range10 to 90% RH (non-condensing)
Weight0.46 lbs (210 g)
Environmental Protection ClassPollution Degree 2 (indoor sheltered)
Touchpoint Pro Analog Input Module mA
Analog Input Module mA
Description4-channel 4-20 mA Analog Input Module with 2 or 3 wire interface to detector
Sensor Configuration4 x 2-wire or 3-wire (current sourced from detector)
Signal Measurement Range0-25 mA
Supply Voltage (Vs)24 Vdc (18-32 Vdc)
Field Device Supply VoltageSupply Voltage (Vs) – 0.7 V
Single Channel Field Device Supply CurrentMaximum 1 A
Total Field Device Supply CurrentTotal Maximum current:2 A at 65°C ambient
Total Maximum current:4 A at 55°C ambient
Power Consumption0.8 W (Excluding sensor supply)
Power DissipationMaximum 3.7 W, at 4 A total field device load
Maximum 2.1 W, at 2 A total field device load
Sense Resistance101 Ω
Connector CodingAnalog Input Module connectors (TB1-TB4) are coded with coding keys to avoid mis-wiring
DIN Rail connector (Module Supply and Communication)Maximum Current:4.04 A (18-32 Vdc)
Touchpoint Pro Analog Input Module mA Terminal Identification
Terminal IdentificationLabelChannelField Device
1+VInput 1+24 Vdc
2SIG4-20 mA signal
3-V0 Vdc
4+VInput 2+24 Vdc
5SIG4-20 mA signal
6-V0 Vdc
7+VInput 3+24 Vdc
8SIG4-20 mA signal
9-V0 Vdc
10+VInput 4+24 Vdc
11SIG4-20 mA signal
12-V0 Vdc
Touchpoint Pro Analog Input Module mV
Analog Input Module mV
Description4-channel Analog Input Module for Catalytic Bridge sensors
Electrical Connection4 x 3-wire mV-Bridge
Supply Voltage24 Vdc (18-32 Vdc)
Sensor Drive methodConstant current
Programmable Current Range180-360 mA
Maximum Loop ResistanceTotal Maximum loop resistance:40 Ω at 200 mA (including Sensor)
Total Maximum loop resistance:27 Ω at 360 mA (including Sensor)
Input Range±15 mV to ±600 mV
Power ConsumptionMaximum 1.2 W (Excluding Sensors)
Power DissipationMaximum 3.5 W
Connector CodingAnalog Input Module connectors (TB1-TB4) are coded with coding keys to avoid mis-wiring
DIN Rail connector (Module Supply and Communication)Maximum Current:1.1 A (18-32 Vdc)
Touchpoint Pro Analog Input Module mV Terminal Identification
Terminal IdentificationLabelChannelField Device
1SInput 1Sensitive (+)
201Signal
3NSNon-sensitive (-)
4SInput 2Sensitive (+)
501Signal
6NSNon-sensitive (-)
7SInput 3Sensitive (+)
801Signal
9NSNon-sensitive (-)
10SInput 4Sensitive (+)
1101Signal
12NSNon-sensitive (-)
Touchpoint Pro Digital Input Module
Digital Input Module
Description4-Channel Digital Input Module for switched input devices
Electrical Connection4 x 2-wire Switch Inputs
Supply Voltage24 Vdc (18-32 Vdc)
Power Consumption1 W maximum (no inputs connected)
Power Dissipation2.8 W maximum
Field Terminals (TB1-TB4) RatingsMaximum current of 14 mA through switched input device at 18-32 Vdc
EOL (End Of Line) Resistance10 kΩ, 0.25 W, ±1%
INL (In-Line) Resistance2.7 kΩ, 0.25 W, ±1%
Switch Input Device supply
Voltage (Vs)
Minimum15 V
Maximum32 V
Switch Input Device supply
Current (Is)
Minimum5 mA for Supervised OC/SC Switch ON condition
Maximum14 mA for Unsupervised Switch ON condition
Connector CodingDigital Input Module connectors (TB1-TB4) are coded with coding keys to avoid mis-wiring
DIN Rail connector (Module Supply and Communication)Maximum Current:95 mA (18-32 Vdc)
Touchpoint Pro Digital Input Module Terminal Identification
Terminal IdentificationLabelChannel
1+Input 1
2
3-
4+Input 2
5
6-
7+Input 3
8
9-
10+Input 4
11
12-
Touchpoint Pro Relay Output Module
Relay Output Module
Description4-channel Relay Output Module incorporating 4 single pole change over (SPCO) relays and 24 Vdc Auxiliary Power Output
Electrical Connection4 x SPCO Relay Terminals (TB1 to TB4)
4 x 2-wire Auxiliary Output Terminals (TB5 to TB8)
Supply Voltage (Vs)24 Vdc (18-32 Vdc)
Auxiliary Supply VoltageSupply Voltage (Vs) – 0.7 V
Auxiliary Supply CurrentMaximum 1.5 A
Power ConsumptionMaximum 1.5 W (excluding auxiliary power consumption)
Power DissipationMaximum 2.3 W
Relay Contacts (TB1-TB4)Maximum 5 A through one relay contact at 250 Vac / 30 Vdc (non-inductive)
Maximum 8 A total through all four relay contacts at 250 Vac / 30 Vdc (non-inductive)
Minimum 12 Vdc, 10 mA
Connector CodingRelay output connectors (TB1-TB4) and auxiliary output connectors (TB5-TB8) are coded with coding keys to avoid mis-wiring.
The relay output connectors (TB1-TB4) are colored black to identify them for AC supply wiring
DIN Rail connector (Module Supply and Communication)Maximum Current:1.62 A (18-32 Vdc)
Touchpoint Pro Relay Output Module Terminal Identification
Terminal IdentificationLabelChannel
1NORelay 1
2NC
3C
4NORelay 2
5NC
6C
7NORelay 3
8NC
9C
10NORelay 4
11NC
12C
13V Aux 1
14+V
15-V
16V Aux 2
17+V
18-V
19V Aux 3
20+V
21-V
22V Aux 4
23+V
24-V

Additional information

Weight 1 lbs