QuadBand IR3+ Detector, 316 Stainless Steel encl., (2) M25 entries, for High Background IR Applications

$5,127.00

Description

FM, cFM, IECEx, ATEX, & INMETRO approved.

FS24X QuadBand 911

The Honeywell FS24X is the latest generation high technology Multi-Spectrum Triple IR (IR/IR/IR/Visible) Flame Detector, which is part of the FSX family of advanced technology Electro-Optical fire detectors. Using patented WideBand IR, WideBand 4.3 micron IR, and Visible detection technology, the FS24X is a quantum leap in flame detection. Sophisticated software algorithms and dual microprocessors ensure that the FS24X has the highest fire detection performance combined with optimal false alarm rejection.

The WideBand IR Infrared technology using high-speed solid-state Quantum sensors allows detection of all types of fires, hydrocarbon and non-hydrocarbon, in all weather conditions. If the detector’s signal is blocked by ordinary window glass, the patented WideBand IR sensors will still alarm to the fire but at a reduced sensitivity and slower response time.

Dual microprocessors provide a high level of fail-safe operation combined with fast and reliable performance. The Master Microprocessor performs high-speed digital sampling and signal-processing calculations: while the slave microprocessor handles various sensor data, performs communications, self-diagnostics and provides interface versatility: and additional memory for storing Event Log and FirePic data.

The FSX family of detectors features Honeywell's patented FirePic data storage and information retrieval facility. FirePic records pre-fire data, which can be recovered from the Detector’s non-volatile flash memory for post fire analysis and postulation of the fire cause. Additionally, unique Real-Time Graphing (RTG) allows viewing of the data that the Detector actually sees. A combination of outputs makes the FS24X a truly versatile detector for today’s demanding industrial requirements.

The FS24X Flame Detector has a detection range greater than 200 feet (Very High Sensitivity setting) for the detection of a one square-foot Heptane reference fire and has a cone of vision far greater in volumetric coverage than any other Multi-Spectrum IR Detector. This means fewer detectors can be used as compared to other manufacturers’ detectors.
• Patented WideBand IR Technology

• Patented Electronic Frequency Analysis

• Visible Sensor for optimum false alarm rejection

• Selectable detection sensitivities

• Field-of-View: 110° full 100% cone-of-vision (90° full 100% cone-of-vision model also available)

• Dual microprocessors for reliable performance

• Real-time clock for accurate time dating of events

• FirePic — pre-fire event data storage

• Event log with date and time stamp

• RS-485 ModBus communication

• Non-Isolated 4-20 mA Analog output (sink or source)

• Alarm, Fault and Fire Verification relays

• Automatic optical path and electronic self-test

• Widest operating temperature range

• Patented Electronics Module for components protection with easy plug-in terminations and field installation

• Two ¾” NPT OR 25mm conduit entries

• Low power consumption

• High RFI and EMI immunity

• FM, ATEX, CE mark approvals

• Meets SIL 2 requirements

• Detects hydrocarbon and non-hydrocarbon fuel fires in all environmental conditions

• User selectable outputs

• Optimal false alarm rejection for all environmental conditions

• Minimal maintenance for trouble-free operation

• PC software and Interface Module (FSIM) for fault diagnostics, real-time graphics (RTGs), and downloading of FirePics and event log

• Suitable for a wide variety of applications

• Easy electronics module replacement

• Test lamps for manual testing
• Refineries and oil production facilities

• Off-shore platforms

• Turbine/Compressor enclosures

• Oil and gas pipelines and pumping stations

• LNG/LPG loading and unloading facilities

• Natural gas and CNG plants

• Ethanol, Methanol, and IPA production and storage

• Crude oil and gasoline storage and tank farms

• Aircraft hangars

• Paint and solvent storage

• Chemical production, storage, and loading facilities

• Power plants
Field of viewFS24X-9:90° cone of vision, ± 45° from on axis
FS24X-2:110° cone of vision, ± 55° from on axis
SensitivityVery high (200 ft.), high (150 ft.), medium (100 ft.) and low (50 ft.) - switch selectable
Response time3-5 seconds to 1 sq. ft. n-Heptane fire at 30 m (100 ft.)
3-10 seconds to (1 sq. ft. n-Heptane fire at 60 m (200 ft.)
Spectral sensitivityVisible:400 – 700 nanometers
Near Band IR:0.7 – 1.1 microns
Wide Band IR:1.1 – 3.0 microns
Wide Band IR:3.0 – 5.0 microns
Operating voltage24 Vdc nominal (18-32 Vdc) - regulated
Power consumptionOperating:56 mA @ 24 Vdc nominal
Alarm:106 mA @ 24 Vdc nominal
Heater:155 mA – additional
Note: Heater will turn on at 0ºF (-17ºC)
Output relaysFire Alarm:SPDT (NO / NC) – De-energized/energized, latching/non-latching
Fault:SPST (NO) – De-energized, latching/non-latching
Auxiliary:SPDT (NO / NC) – De-energized/energized, latching/non-latching
Contacts rating:1 amp @ 24 Vdc
Analog output0 - 20 mA stepped - source or sink user selectable
Loop resistance50 - 400 Ohms
CommunicationOne of the following – user selectable:• RS-485, ModBus Protocol
• RS-485, FireBus II
• HART, Optional plug-in module (not available on EN54-10 units)
Visual indicationsGreen LED:Power
Red LED:Alarm
Yellow LED:Fault
Temperature rangeOperating:110° Field of View FS24X: -40ºF to +185ºF (-40ºC to +85ºC)
90° Field of View FS24X: -60°C to +85°C (-76°F to +185°F)
Storage:-67ºF to +230ºF (-55ºC to +110ºC)
Humidity range5 to 98% relative humidity, non-condensing
VibrationMeets or exceeds MilSpec 810C Method 514.2, Curve AW12
Wiring14 AWG to 22 AWG; shielded cable recommended
Conduit entriesStandard:Two M25 or two ¾" NPT
Enclosure materialsCopper-free powder coated aluminum or 316 stainless steel
Enclosure typeIP66 and NEMA 4 & 4X
CertificationsFM:Class I, Div. 1 & 2, Groups B, C, & D; Class II, Div. 1 & 2, Groups E, F, & G; Class III
ATEX/IECEx:Ex II 2 G Ex db IIC T4 (Ta: -60 to +110°C), T5 (Ta: -60 to +75°C), T6 (Ta: -60 to +60°C), II 2 D Ex tb IIIC T135°C (FS24X-9, 90° Field of View)
Ex II 2 G Ex db IIC T4 (Ta: -40 to +110°C), T5 (Ta: -40 to +75°C), T6 (Ta: -40 to +60°C), II 2 D Ex tb IIIC T135°C (FS24X-2, 110° Field of View)
CE:Complies with EN6100-6-4 & EN50130-4
INMETRO
CU-TR
SIL Rating:FMEDA available on request
EN54-10:FS24X-9 certified 1175a/02 (LPCB); CPR 0832-CPR-F0516
Shipping weightAluminum:3.6 lbs (1.6 kg)
Stainless steel:7 lbs (3.2 kg)
MountingSwivel bracket assembly - optional
WarrantyThree years from date of shipping

Additional information

Weight 7 lbs
Dimensions 4.35 × 6.15 × 4.89 in